8. Configuration via display and operating unit
Linearisation table
Will be used for special designs. The linearisation table can, as an option, be loaded at
the factory or can be transferred via HART
EN
8.5 Setting the units
8.5.1
Setting the pressure unit
1. Open the operating menu with [↵].
Select "Basic setting" and confirm with [↵].
2. Select "Application" and confirm with [↵].
3. Select "Pressure" and confirm with [↵].
4. Select "Unit" and confirm with [↵].
5. Select pressure unit and confirm with [↵].
» Pressure unit is set.
34
®
.
WIKA operating instructions, model DMSU21A