Technical specifications

Flow rate max. (100% water)
Service
Accuracy up to 15 PSID = 100
kPa
Minimum ΔP for start-up
Maximum ΔP
Maximum working pressure
Close off pressure
Temperature
Connection
Leakage
Compliance
Flow rate max. (100% water)
Service
Accuracy up to 15 PSID = 100 kPa
Minimum ΔP for start-up
Maximum ΔP
Maximum working pressure
Close off pressure
Temperature
Connection
Leakage
Compliance
Table 1: VP10x Hxx
VP10xHAA
150 l/h
Water or water-glycol mixture (up to 50% glycol), quality to VDI 2035
25 kPa
Johnson Controls declares that these products are in compliance with the essential
requirements and other relevant provisions of the PED (Pressure Equipment Directive) 2014/68/
UE (Paragraph 4, comma 3).
CE Marking is not applicable.
ROHS (95/2002/CE)
Table 2:
VP10x Jxx 3/4" (DN20)
VP10xJAJ
1,000 l/h
Water or water-glycol mixture (up to 50% glycol), quality to VDI 2035
Johnson Controls declares that these products are in compliance with
the essential requirements and other relevant provisions of the PED
(Pressure Equipment Directive) 2014/68/UE (Paragraph 4, comma 3).
CE Marking is not applicable.
ROHS (95/2002/CE)
15
1/2" (DN15)
VP10xHDA
450l/h
± 5%
35 kPa
600 kPa
2500 kPa
689 kPa
-10 to 120 °C
Rp 1/2" F
ANSI Class IV IEC 60534-4
± 5%
25 kPa
600 kPa
2500 kPa
689 kPa
-10 to 120 °C
Rp 3/4" F
ANSI Class IV IEC 60534-4
VP10xHDC
850 l/h
25 kPa
VP10xJDB
1,850 l/h
30 kPa