9. Control Panel
Output Voltage
Bypass Voltage Range
Bypass Frequency Range
Converter Mode
ECO Mode
Bypass Mode
Auto Restart
Cold Start
Battery Mode Delay Time
System Shutdown Time
System Restore Time
Redundancy
9.3.6.3 Battery
The SETUP – BATTERY screen may be accessed in any UPS operating mode. Some settings may only be amended in certain modes; refer to table
9.5 for details.
BATTERY CAPACITY IN Ah
BATTERY
16-11-183-9334F8.indb 25
SmartOnline SVX-Series UPS Operating Mode
Standby
Bypass
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Maximum Charging Current
MAXIMUM CHARGING
CURRENT
Battery Shutdown Voltage
BATTERY LOW /
SHUTDOWN SETTING
BATTERY TEST
BATTERY AGE ALERT
TEMPERATURE
COMPENSATION
Stop by Battery Capacity
Line
Battery
Battery Test
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Table 9.4
Set battery capacity (0-999) (Default: 009)
Battery Capacity in Ah
Set maximum battery charging current (1-64A)
(Default: 2)
Set battery low voltage: (10.5-11.5V) x
Battery Low Voltage
(number of batteries) (Default: 220V)
Set battery low capacity (20-50%) (Default: 20%)
Battery Low Capacity
Set voltage point for system shutdown (10-11V) x
(number of batteries) (Default: 200)
Set 'Disable' or 'Enable' (Default: Disabled)
Periodic Battery Test
Set battery test interval (7-99 days) (Default: 30)
Battery Test Interval
Set testing time for battery test (10-1000 sec)
Stop by Time
(Default: 10)
Set battery voltage cut-off to end battery test
Stop by Battery Voltage
(11-12V) x (number of batteries) (Default: 220V)
Set battery capacity cut-off for battery test (20-50%)
(Default: 20)
Set battery age for replacement alert
Battery Age Alert
(Disable, 12-60 months) (Default: Disabled)
Temperature
Set battery compensation (-5~0)
Compensation
(Default is 0)
25
Fault
Converter
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
ECO
Y
Y
Y
Y
Y
Y
Y
1/18/2017 9:53:24 AM