THERMOSTAT CONTROL 0-100%

For fan coils with a brushless motor, the 0 -10V signal profile will be as shown below:
THERMOSTAT-CONTROLLED VENTILATION
With adjustment on the basis of thermostat-controlled ventilation (dip 3 OFF), the ventilation function switches off when the set value
is reached.
CONTINUOUS VENTILATION
Continuous ventilation is selected by setting dip 3 ON. In this mode, ventilation continues at the selected speed even after the
set temperature value has been reached. This function is disabled if the machine has no shut-off valve (dip 1 OFF); in this case,
ventilation is always managed via thermostat-control logic. The following table shows the ventilation speed activated according to the
position of the selector:
Selector
The thermostat is switched off. It can start up in Heating mode however, if the room temperature falls below 7°C and the water
OFF
AUTO
V1
In this position, the minimum ventilation speed V1 remains active, regardless of the thermostat requests.
V2
In this position, the average ventilation speed V2 remains active, regardless of the thermostat requests.
V3
In this position, the maximum ventilation speed V3 remains active, regardless of the thermostat requests.
Aux
GRADUAL VENTILATION START-UP
The thermostat offers gradual fan start-up control when the fan coil is enabled, to guarantee better environmental and acoustic
comfort (refer to the figure below).
THE START-UP CONDITIONS MAY BE AS FOLLOWS:
Electrical activation of the fan coil with the operating mode selector in any position other than OFF.
Activation of the fan coil by rotating the operating mode selector from OFF to AUTO, V1, V2, V3 or AUX.
Closure of the MS contact if used for external enabling (dip 4 OFF), and from the CE input.
26
AVMFE19LJ 2011 - 5779300_05
Thermostat control
Heating setting
temperature is suitable (anti-freeze function).
When the set value is reached, ventilation continues at the minimum speed (V1).
In this position, the minimum ventilation speed V1 remains active.
100%
Ventilation
activation
0%
adjustment range
0-100%
Dead
band
Cooling setting
Function
2 min
AmbT [°C]
time