Series star connection
U1
STANDARD
T1
USA MARKET
The internal connection diagrams of the generators can be found at the end of this manual for standard 7 clamp
(12 terminal) generators.
Fix the output cables to the generator clamps as shown in Figure 6:
Rotation direction
Generators are normally supplied in a clockwise rotation configuration (as seem from the coupling side).
Connection to ground
Inside the terminal box there is a terminal for ground connection, while a second terminal is located on a foot of
the generator. Perform grounding with a copper wire of suitable section, according to the applicable standards.

5.7 Single-phase loads

The 3-phase generators of this series can be used as single-phase, taking into account the indications provided
below:
The generator can be used for a maximum power equal to 0.6 times the power specified on the
nameplate for the 3-phase load.
The generator can be connected according to a star pattern in parallel (required voltage 220 Volt at 50 Hz or
220-240 V at 60 Hz) and the single-stage load must be connected to clamps U1/T1 and V1/T2.
963857252_=
Connection diagrams for standard generators
CABLE MARKING
V1
W1
U2
V2
T2
T3
T4
T5
LINE
YES
Parallel star connection
LOAD
Parallel star connection
W2
U5
V5
W5
T6
T7
T8
T9
WINDING
U6
V6
W6
T10
T11
T12
LINE
NO
Fig. 6
Fig. 7
37