ENG
NOTE
Protective conductors in the mains connection cable are not regarded as potential equalization conductors.
Prerequisite
DANGER – Danger to life due to electric shock. Make sure that the unit is voltage-free.
•
All general requirements for safe and reliable operation are fulfilled.
Procedure
1.
Make the mains connection according to the circuit diagram, see chapter "Electrical circuit diagram – Standard-Controller
(SC)", Page 39.
2.
Open the cage clamp terminal of the connecting plug with the flat screwdriver and connect the cables on the plug.
–
Firmly insert the screwdriver into the cage clamp terminal. Never turn, this will damage the cage clamp terminal.
3.
Before switching on, make sure that the mains voltage matches the data on the type plate and that there is a right-hand
field of rotation.
The cooling unit is connected electrically.
4.6.7
Adapting the unit to the mains voltage
NOTE
Only cooling units with a rated voltage of 400 / 460 V, 3~ can be optionally connected to another mains voltage.
•
Cooling units with the rated voltage 230 / 115 V, 1~ have no transformer options. No adjustment of the upstream fuse
is therefore required.
Operating Manual | Roof-mounted Cooling Unit | Standard Controller (SC) – 230 V | 086100022c
46/47