4.6.8

Adapting the unit to the mains voltage

Factory settings control transformer
Fig. 25: Adapting the mains voltage on the control transformer
Units with a mains voltage of 400/460 V can be connected optionally to another mains voltage.
The mains voltage on the transformer must be adapted for this.
The adaption is made by replugging the supply cable on the primary side of the transformer.
The upstream fuse must match the changed mains voltage, see the "Upstream fuse" column in
The data for the transformer factory settings can be found on the yellow connection diagram (1) on the rear of the unit.
UL-conform with following fuses: Category "ClassCC", slow-blow.
Mains voltage
50 Hz
60 Hz
400 V
460 V
Tab. 9: Transformer options and upstream fuse
Operating Manual | Roof-mounted Cooling Unit | Multi Controller (MC) – 400 V, 3~ | 086100035c
Transformer
Input winding
T1/ 1 [0] – T 1/ 4 [400]
T1/ 1 [0] – T 1/ 7 [460]
L2
L1
Input winding control transformer
Upstream fuse
(Min. 480 V)
Max. 2.5 A
G00057
Fig. 25
Max. 4 A
50/51