Operation
UPS Settings
continued
Battery Charger Settings
From the SETUP MENU screen, scroll DOWN to access the CHARGER SETTING screen. From the CHARGER SETTING screen,
press ON to get to the CHARGER CURRENT screen. Press ON again, then scroll UP or DOWN to select charger current values between
1.5A and 4.0A. Press ON to save the desired value. Warning: Do not change this setting unless otherwise instructed.
Battery Test Settings
This setting is used to set the time period between deep discharge tests. From the SETUP MENU screen, scroll DOWN to access the
BATTERY SETTING screen. Press ON to access the BATTERY LOW ALARM screen and scroll DOWN until you reach the DEEP
DISCH TEST screen, then press ON. Scroll UP or DOWN to choose the setting: NO TEST, 30 DAYS, 60 DAYS, 90 DAYS or QUICK
TEST. Press ON to save the setting. The default setting is NO TEST.