Control
Amplifier
5. Install Electrical Outlets
WARNING: Risk of electric shock. Disconnect the power before performing the following
procedures.
NOTICE: A qualified electrician must install two GFCI- or RCD-protected, 120 V, 15 A grounded outlets.
Both outlets may share the same electrical service, but no other load should be on this circuit.
Install a 120 V, 15 A grounded outlet within the wall framing and within 24" (610 mm) of the
planned control amplifier location. Route the wires through conduit for this outlet installation.
Install a 120 V, 15 A grounded outlet near the control board end of the bath and within 24" (610
mm) of the junction box.
Kohler Co.
24" (610 mm)
Maximum
Conduit
120 V, 15 A
Grounded Outlet
13
120 V, 15 A
Grounded Outlet
24" (610 mm)
Maximum
Control
Board
Junction
Box
1297610-2-B