Tabla de contenido
Idiomas disponibles

Idiomas disponibles

6. Configuration and Operation
6.1.2 Automatic Transfer Switch Source Selection
The ATS will power up and supply output if at least one of the inputs is greater than the minimum
startup voltage. In normal operation, when both sources are of equal quality ("fair" or "good"), the
unit will select the preferred source according to the preferred source selection setting (Refer to the
Navigating Config Menus and Submenus section). If the currently selected source degrades to a
quality less than the currently unselected source, the unit will transfer to the better quality source.
If the currently unselected source improves in quality greater than the currently selected source,
the unit will transfer to the better quality source.
Nominal Voltage
Minimum Startup Voltage
Good Voltage Range
Fair Voltage Range
Bad Voltage Range

6.1.3 Quick Test

After installing the ATS and connecting equipment, you may test
the Automatic Transfer Switch function by temporarily disabling the
preferred AC input (default is Source A). The ATS will then switch
from the preferred input to the alternate input. When the preferred
input resumes supplying power, the ATS will switch back to the
preferred input.
Note: The two inputs must be connected to separate sources of utility
power. The automatic transfer switch function will be compromised if the
two inputs are connected to the same power source. Do not perform a test
with equipment that must remain in productive operation. Any test
procedure must prepare for the contingency that the equipment may lose
power. Do not test the ATS by detaching power cords which are connected
to live power sources, as this eliminates the connection to ground and
places your equipment at risk.
15-09-215-93338F.indb 16
Input Voltage Ranges
200-240V
163V
172-266V
144-171V
0-143V
Preferred Source (A) Active
Alternate Source (B) Active
16
9/30/2015 4:56:33 PM
Tabla de contenido
loading

Este manual también es adecuado para:

Pdumnh20hvatPdumnh30hvatPdumnh32hvatAg-0135Ag-0134Ag-012f

Tabla de contenido