4
Technical description of the burner
4.1
Technical data
MODEL
CODE
OUTPUT
2nd stage°
(1)
DELIVERY
(1)
1st stage°
FUEL
- Net calorific value
- Density
- Viscosity at 20 °C
OPERATION
NOZZLES
STANDARD APPLICATIONS
AMBIENT TEMPERATURE
COMBUSTION AIR TEMPERATURE
PUMP J7C
delivery (at 12 bar)
pressure range
fuel temperature
NOISE LEVELS
(2)
Reference conditions: Ambient temperature 20 °C - Barometric pressure 1000 mbar - Altitude 100 m a.s.l.
(1)
Sound pressure measured in manufacturer's combustion laboratory, with burner operating on test boiler and at maximum rated
(2)
output.
4.2
Electrical data
CODE
POWER SUPPLY
ELECTRICAL MOTOR IE2
Operating current
Acceleration current
IGNITION TRASFORMER
ELECTRICAL POWER CONSUMPTION
ELECTRICAL PROTECTION
6080
Technical description of the burner
kW
Mcal/h
kg/h
kW
Mcal/h
kg/h
kWh/kg
Mcal/kg
3
kg/dm
2
mm
/s max
Two-stage (high and low flame) and single-stage (all - nothing).
number
°C
°C max
kg/h
bar
°C max
dBA
V
400 with neutral ~ +/- 10%
Hz
rpm
W
V
A
A
V1 - V2
I1 - I2
W max
6
GB
RL 190
3475614
1423 - 2443
1224 - 2100
120 - 206
759 - 1423
653 - 1224
64 - 120
LIGHT OIL
11,8
10,2 (10.200 kcal/kg)
0,82 - 0,85
6 (1,5 °E - 6 cSt)
Intermittent (min. 1 stop in 24 hours).
2
Boilers: water, steam, diathermic oil
0 - 40
60
230
10 - 21
90
83,9
3475614
50 - three-phase
2900
4500
400
8,7
81
230 V - 2 x 5 kV
1,9 A - 35 mA
5500
IP 44
20011018
20011018
230 with neutral ~ +/- 10%
50 - three-phase
2900
4500
230
15
141