4. If you wish to abort the test while it is underway, follow these steps:
a.
Display the user parameter list by pressing
b.
Use the arrow keys to scroll through the parameters until the display shows "Battery
capacity test: xxx."
c.
Switch the battery capacity test "OFF" by pressing
5. Wait until the display shows "Normal operation load power xx%" and a short alarm
sounds.
6. Press
. The display will show "Battery capacity test: xxx." ("xxx" = the estimated
backup time in minutes)
7. Press
to exit the user parameter list.
304 Internal Bypass Switch (50 Hz Models Only)
50 Hz UT310-UT3100 models include an internal bypass switch inside the front door. This
switch is not the recommended method of bypassing the UPS if the unit is being
serviced. Use an external maintenance bypass switch for 100% isolation of the UPS. If the
UPS is not being serviced, you may change the internal bypass switch position to "By-pass"
to operate your load equipment directly from mains AC line power. The display will show
"Bypass operation," and the "System in man. bypass" alarm will be active. (See Section 206.)
Use the "normal" position when you want your load equipment to receive power from the
UPS.
If the unit is being serviced, use an external maintenance bypass switch.
Hazardous voltages are present inside the unit even when the internal bypass
switch is in the "By-pass" position.
S0 0 1
S0 0 2
.
CAUTION
Internal
Manual
Bypass
BA TTERY X003
1
2
L+
L-
25
.
UT340-3100