8 - CONTROL UNIT
PD22 is provided with a display that, not only makes
programming simple, but also allows a continuous monitoring of
the input statuses; in addition, thanks to a menu structure, the
working schedule and the operation logic can be set easily.
In compliance with the European standards concerning
electrical safety and electromagnetic compatibility
(EN 60335-1, EN 50081-1 and EN 50082-1) it has been
equipped with the low voltage circuit total electric insulation
(motors included) from the network voltage.
Other characteristics:
•
Power supply protected from short circuits within the
controller, on the motors and on the connected accessories.
•
Detecting obstacles by monitoring the current on the motors
(current sensing probe and encoder)
•
Automatic learning of the limit switches position.
•
Tests for safety devices (photocells, safety edges and mosfet)
before each opening.
•
Deactivation of safety inputs through the configuration menu:
no jumper is required for terminals concerning safety devices
that have not been installed, yet. You will only need to disable
this function from its relevant menu.
•
Low voltage output that can be used for a signal light or a
24V flashing light.
•
Built-in LED courtesy light.
•
ENERGY SAVING function
m
WARNING: Installation of control unit and safety
devices must be carried out with power disconnected
8.1 - ELECTRICAL CONNECTIONS
L1
Antenna
L2
Antenna shield
Input for N.O. contacts to start the cycle, configurable
as:
L3
- Start: opening closure command
- Open: controls opening only
L4
Photocell. N.C. contact (disabled by default)
Input for safety devices or closure button, configurable
as:
L5
- STOP button. N.C. contact (disabled by default)
- Safety rib (disabled by default)
- N.A button to control closure (disabled by default)
L6
Common (-)
L7
+24Vdc supply for photocells and other accessories
L8
Accessory power common (-)
+24Vdc supply - photocell/optical edge TX for
functional Test.
L9
Connect power supply cables of photocells
transmitter between terminals L7 and L8
L10
Flashing light 24V / Warning light 24V (+)
L11
Flashing light 24V / Warning light 24V (-)
BATTERY
B-PACK or ECO-LOGIC back-up battery pack
RECEIVER
Connector for MR receiver
OVERLOAD Overload LED indicator light on supply line
G1
Anomaly signalling LED
Automation status LED indicator light
STAND-BY: 1 blink every 2"
G2
OPENING: flashing 2Hz
CLOSING: flashing 2Hz
PAUSE: lit
- 32 -