ELECTRICAL CONNECTIONS

• Locate control box: within sight of door but away from all moving parts of the door and at a height of more than 1.4m above the
ground out of the reach of children
• Connect the ground wire of the system to the ground terminal of the actuator marked by the symbol
• If the door is equipped with mechanical stop, install a safety contact on the stop and connect the terminals of the contact to the
STOP input of the control unit
MOTOR TERMINALS
LS - LS
OP
CO
CL
W
V
U
CONTROL UNIT TERMINALS
N.C. dry contact for connecting a OPEN DOOR LIGHT
Opening limit switch
Limit switch common
Closing limit switch
PHASE 1 / OPENING
PHASE 2 / CLOSING
PHASE 3 / COMMON

CONTROL UNIT

V1
Opening limit switch 1
V2
Opening limit switch 2
V3
Opening limit switch 3
R1
Closing limit switch 1
R2
Closing limit switch 2
ST
Security contact - hand chain
SC
Security contact - thermal protection
13
GREEN
LIMIT CAM
RED
LIMIT CAM