RAGGIO C
Fault code
Fault
Sensor control protection
F36
activation
A42
Exchanger protection
F43
intervention.
Water pressure sensor
F47
error
Low water pressure with
F51
parameter b06 = 3
Limit thermostat fault with
F50 - F53
parameter b06 = 1 or 4
Calibration fault
F57 - A56
Calibration procedure not
completed
Controller fault
F58 - A61
A54 - A55 - A63 Controller fault
F67
BCC Service key error
F65 - A68
No communication
between controller and
A62
gas valve
Maximum number of con-
secutive Resets
A64
exceeded
F66
EN
Possible cause
Return and/or flow sensor
damaged or disconnected
Return sensor damaged or
disconnected
No system H
O circulation Check the circulating pump
2
Air in the system
Water pressure sensor
disconnected
Water pressure sensor
damaged
Pressure too low
Secondary water pressure
switch disconnected or
damaged
Incorrect parameter
No/poor water circulation
in the system
Air in the system
Incorrect parameter
Incorrect parameters
Electrode damaged or not
correctly positioned.
Recirculation of fumes
inside the boiler
Poor primary circuit circu-
lation or poor dissipation
during calibration
Controller internal error
Controller internal error
BCC Service key con-
nected
Error loading BCC Service
key file
Controller not connected
Valve damaged
Maximum number of con-
secutive Resets exceeded
Firmware not loaded suc-
cessfully
cod. 3541V280 - Rev. 00 - 03/2021
Cure
Check the correct positioning and oper-
ation of the return and/or flow sensor
Check the correct positioning and oper-
ation of the return sensor
Vent the system
Check the water pressure sensor wiring
Check the water pressure sensor
Fill the system
Check the water pressure switch/pres-
sure transducer
Check the correct parameter setting
Check the circulating pump
Vent the system
Check the correct parameter setting
Check parameters and carry out a
100% calibration
Check the position of the electrode,
replace it if necessary. After replace-
ment, repeat the 100% calibration
Check the tightness of the flue pipe and
the seal of gaskets
Reset the fault. Turn on the hot water
faucet and wait for the flame to stop
flashing (about 2 minutes)
Check the ground connection.
Check the electrode.
If necessary replace the control unit.
Try disconnecting the power supply to
the boiler for 10 seconds and replace
the controller if necessary
Load the parameters
Repeat the loading procedure within 5
minutes from the boiler power supply
and replace the BCC Service key if
necessary
Connect the controller to the valve
Check the wiring
Replace the valve
Turn off the power to the boiler for 60
seconds and then reinstate the boiler
Reload the firmware or replace the card
203