Sensors

The sensors installed have the following characteristics:
– Dual sensor (thermal safety/output) NTC R25°C; 10kΩ β25°-
85°C: 3435
– domestic hot water sensor NTC R25°C; 10kΩ β25°-85°C: 3435
– external sensor NTC R25°C; 10kΩ β25°-85°C: 3435
Correspondence of Temperature Detected/Resistance
Examples of reading:
TR=75°C → R=1925Ω
TR=80°C → R=1669Ω.
TR
0°C
1°C
2°C
3°C
0°C 27279
26135
25044
24004
10°C
17959
17245
16563
15912
20°C
12090
11634
11199
10781
30°C
8313
8016
7731
7458
5828
5630
5440
5258
40°C
50°C
4161
4026
3897
3773
60°C
3021
2928
2839
2753
2229
2164
2101
2040
70°C
80°C
1669
1622
1577
1534
1266
1232
1199
1168
90°C
973
100°C
1.8

Expansion vessel

The expansion vessel installed on the boilers has the following
characteristics:
Description
Total capacity
Prefilling pressure
Useful capacity
Maximum system
content (*)
(*) Conditions of:
Average maximum temperature of the system 85°C
Start temperature at system filling 10°C.
m
CAUTION
– For systems with water content exceeding the
maximum system content (as indicated in the
table) an additional expansion vessel must be
prearranged.
– The difference in height between the relief valve
and the highest point of the system cannot exceed
6 metres. If the difference is greater than 6 metres,
increase the prefilling pressure of the expansion
vessel and the system when cold by 0.1 bar for each
meter increase.
70
4°C
5°C
6°C
7°C
8°C
23014
22069
21168
20309
19489
18706
15289
14694
14126
13582
13062
12565
10382
9999
9633
9281
8945
7196
6944
6702
6470
6247
5082
4913
4751
4595
4444
3653
3538
3426
3319
3216
2669
2589
2512
2437
2365
1982
1925
1870
1817
1766
1491
1451
1411
1373
1336
1137
1108
1079
1051
1024
Brava One HE ErP
U/M
25
30
35
l
9,0
kPa
100
bar
1,0
l
5,0
l
124
1.9

Circulation pump

The flow-head performance curve available for the heating
system is shown in the graph below.
m
CAUTION
The appliance is equipped with a by-pass which
ensures water circulation in the boiler when the
thermostatic valves or cocks are used in the system.
RESIDUAL HEAD (mbar)
600
9°C
500
400
8622
300
6033
200
4300
3116
100
2296
0
1717
0
200
1300
998
40
10,0
6,0
140
35 40
25
400
600
800
1000
FLOW (l/h)
EN
30
1200
Fig. 5
Tabla de contenido
loading

Este manual también es adecuado para:

Brava one he 30 erpBrava one he 35 erpBrava one he 40 erp

Tabla de contenido