Unscheduled Maintenance; Malfunction Codes And Possible Solutions - Sime Brava One HE 25 ErP Manual De Instalación Y Mantenimiento

Calderas murales de condensación
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

EN
4.5

Unscheduled maintenance

If replacing the electronic board , the user MUST set the
parameters as indicated in the table and in the sequence shown.
Type
No.
Description
Index showing boiler power in kW
tS
0.1
0 = 24; 1 = 25; 2 = 30; 3 = 35; 4 = 40
Hydraulic configuration
0 = rapid
1 = storage tank with thermostat or
heating only
tS
0.2
2 = hot water tank with sensor
3 = bithermic
4=instant with solar power input
5 = open vent
Gas Type Configuration
tS
0.3
0 = G20; 1 = G31; 2 = G230
To enter "Parameter setting and display"refer to the indications
provided in the specific section.
Once the parameters in the table have been set, you must carry
out the entire phase of "Self-calibrating procedure" described
in the specific section.
If the gas valve and/or the ignition/detection electrode , and/or the
, and/or the fan are replaced, the user must still carry out
burner
the entire phase of "Self-calibrating procedure" described in
the specific section.
4.6

Malfunction codes and possible solutions

LIST OF MALFUNCTION/FAULT ALARMS
Type
No.
Fault
AL
01
Smoke thermostat
Low water pressure in
AL
02
system
Domestic hot water
sensor fault (return
AL
04
sensor fault for T
models)
AL
05
Delivery sensor fault
AL
06
No flame detection
Sensor or safety
AL
07
thermostat intervenes
Fault in the flame
AL
08
detection circuit
No water circulating in
AL
09
the system
Setting for
Brava
One HE ErP
24 25 30 35 40
0
1
2
3
4
0
0 or 1 or 2
Solution
- Contact the Technical
Assistance Centre
- Restore pressure
- Check for any leaks in the
system
- Check connections
- Check the sensor is
working
- Check connections
- Check the sensor is
working
- Check the integrity of the
electrode and check that it
is not grounded
- Check gas availability and
pressure
- Check the integrity of the
gas valve and the card
- Check the sensor or
thermostat connections
- Deaerate the system
- Check the bleed valve
- Replace the sensor or the
thermostat
- Check that the pump
impeller is not blocked
- Check the integrity of the
electrode and check that it
is not grounded
- Check the integrity of the
gas valve and the card
- Check the rotation of the
pump rotor
- Check the electrical
connections
- Replace the pump
Type
No.
Fault
AL
10
Auxiliary sensor fault
Gas valve modulator
AL
11
disconnected
Domestic hot water
AL
12
sensor fault in tank mode
AL
13
Smoke probe intervention
AL
14
Smoke probe fault
Fan check cable
AL
15
disconnected
AL
18
Condensate level fault
Maximum number of
AL
28
consecutive resets
reached
Return sensor fault (boiler
AL
30
sensor fault for T models)
Fault due to low network
AL
37
voltage
Incorrect network
AL
40
frequency detected
Flame loss more than 6
AL
41
consecutive times
AL
42
Button fault
Open Therm
AL
43
communication fault
Gas valve timeout fault
AL
44
without flame
Lock for ∆T delivery/
AL
56
return over max limit
(open vent)
Lock for flow temperature
AL
57
(FT) check (open vent)
Self-calibrating procedure
AL
62
is required
Incorrect positioning of
AL
72
the delivery sensor
Second delivery sensor
AL
74
fault
EV2 SGV current max/min
AL
77
absolute limits error
EV2 SGV current upper
AL
78
limit error
EV2 SGV current lower
AL
79
limit error
Fault on the valve control
AL
80
logic line/valve cable
damaged
Solution
- Check the hydraulic
configuration using "tS
0.2"
- Check the electrical
connection
- Check the electrical
connection
- Set the parameter
tS 0.4 (Combustion
configuration) to 0
- Check the sensor is
working
- Replace the smoke
probe
- Replace the smoke
probe
- Check the electrical
connection of the smoke
probe
- Contact the Technical
Assistance Centre
- Check the connection
cable between the fan
and the board
- Check for any clogging
in the pipe which takes
the condensate to the
siphon
- Check that the siphon is
not clogged
- Wait 1 hour and try
unblocking the board
again
- Contact the Technical
Assistance Centre
- Replace the return
probe
- Check parameters
- Contact the Technical
Assistance Centre
- Check the voltage
- Contact your network
provider
- Contact your network
provider
- Check the ignition/
detection electrode
- Check the gas supply
(open valve)
- Check mains gas
pressure
- Check that buttons are
working
- Check the OT electric
connection
- Check gas valve and
board
- Contact the Technical
Assistance Centre
- Contact the Technical
Assistance Centre
- Carry out the self-
calibrating procedure
(see the specific section)
- Check delivery sensor
operation and position
- Check second delivery
sensor operation and
position
- Check gas valve and
board
- Check gas valve and
board
- Check gas valve and
board
- Check gas valve and
board
89