Select The Save Mode You Want To Use; 16- And 24-Zone Grx Control Units - Lutron GRAFIK Eye 4000 Serie Manual De Instalación

Ocultar thumbs Ver también para GRAFIK Eye 4000 Serie:
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 29

Select the Save Mode You Want to Use

Save modes enable you to specify how buttons on the control unit work. For example, adjustments to a zone's 
settings can be temporary or saved for the current scene. Buttons can also be disabled to prevent accidental 
changes.
Select Sd
2
ZONE 5
ZONE 6
Code
Stands for
Sd
Save by Default 
Sb
Save by Button 
Sn
Save Never 
4S
Four Scenes 
bd
Button Disable 

16- and 24-Zone GRX Control Units

The 16 and 24 zone GRAFIK Eye control units offer an expanded number of zones that can be controlled from a 
single wall station. The zone intensity LEDs on the GRX-4x16 or GRX-4x24 will display the light level of a set of 
eight zones at a time. Other sets of zones may be displayed and controlled by pressing the Zone Select Button. 
Addressing
The GRX-4x16 and the GRX-4x24 control units take multiple, consecutive addresses. The GRX-4x16 control unit 
takes up two consecutive addresses, and the GRX-4x24 control unit requires three. To ensure there are sufficient 
addresses available, any GRX-4x16 and/or GRX-4x24 control units in the system should be addressed first. 
Assigning Zones
When assigning zones use the chart below as a guide to see how zones are displayed on the Circuit Selector. The 
chart is for a 24-zone control unit, which uses three addresses. A 16-zone control unit uses only two addresses.
Control Unit Addresses
A1, A2, A3 
A2, A3, A4 
. 
. 
. 
. 
. 
. 
A6, A7, A8 
R
3
Select  
save mode
FADE
TEMPORARY
ZONES
M S
MASTER
Enter  
(exit) 
setup 
mode
Description
  C hanges to a zone's intensity/shade position or fade time are saved for the current scene. 
To make temporary adjustments in Sd mode, refer to page 19. Typical user: Home theater 
owner.
  T EMPORARY ZONES LED is normally ON and all intensity/shade position and fade changes 
are temporary unless the TEMPORARY ZONES LED is turned OFF with the TEMPORARY 
ZONES button. Typical user: Restaurant manager.
  T EMPORARY ZONES LED is permanently ON and cannot be turned OFF. In this mode, all 
intensity changes are temporary. Typical user: Lighting designer.
  A llows only the four SCENE buttons, OFF button, IR receiver, and MASTER 5 or 6 buttons 
to operate. All other buttons on the control unit are disabled. Typical use: Rented meeting 
space.
  A ll buttons on the control unit are disabled. IR receiver and wallstations are still functional. 
(Setup mode is still accessible by repeating Step 1.) Typical use: Public space.
Zones on Control Unit
1-8 
9-16 
17-24 
1-8 
9-16 
17-24 
. 
. 
. 
. 
1-8 
9-16 
17-24 
To select the save mode you want to use:
1. Enter setup mode. Press and hold the SCENE 1 and 
OFF buttons for about three seconds until scene LEDs 
start cycling.
2. Select Sd. Press the FADE 5 button until Sd is dis-
played in the FADE window.
3. Select save mode. Press the MASTER 5 or 6 
button to scroll through the save modes and select 
one. Refer to the save mode descriptions in the table 
1
4
below.
,
4. Exit setup mode. Press and hold the SCENE 1 and 
OFF buttons until scene LEDs stop cycling.
Circuit Selector Display
A11-A18 
A21-A28 
A31-A38 
A21-A28 
A31-A38 
A41-A48 
. 
. 
. 
. 
A61-A68
A71-A78
A81-A88
GRAFIK Eye
 4000 Series Control Unit Installer's Guide     21
®

Solución de problemas

loading

Este manual también es adecuado para:

Grafik eye 4100Grafik eye 4500