Installing the IntelliFlow
WARNING
!
Power MUST be off during installation or servicing of
the valve!
Do not plug valve into supply circuit until completion of
assembly.
NOTICE
For Vertical Installation Only!
1. Shut off electrical power supply.
2. Shut off both hot and cold water supply lines.
3. Remove trim plate (Figs. No.5 & 6) and set aside until
you've completed wall finishing (painting, wall papering,
paneling, etc.).
4. Install the four mounting tabs provided in slots on the sides
of the wall box enclosure (Fig. No. 7).
5. Position the A2C-WB-M1 between the wall studs as shown
in Fig. No. 7. Check that it is level and fasten the mounting
tabs to the studs.
6. Remove drain plug knock out. Install drain piping and water
supply piping to the appropriate IntelliFlow
Either IntelliFlow
®
connection may be used for the hot or
cold water supply.
NOTICE
Excessive heat from soldering can damage plastic components.
Use a heat sink to prevent damage.
7. Place O-rings on adapter grooves (Figure No. 3A).
8. Align and slip the valve body over adapters. Tighten adapter
nuts.
NOTICE
Do not over tighten nuts.
To avoid cross threading, check thread alignment.
9. Prior to installing wall materials, turn on water supply (both
hot and cold) and test for leaks. Test drain piping for leaks.
10. Turn off water supply until you've completed installing
wall materials.
NOTICE
Installation must comply with local codes and ordinances.
Inspection and approval of installation by local authorities may
be required prior to installation of wall material. Check with local
plumbing authorities for requirements.
11. Once you've finished the wall, install trim plate, connect
washing machine water supply hoses to the IntelliFlow
valve and to the washing machine.
12. Plug washing machine into the IntelliFlow
NOTICE
Appliance current rating must not exceed 15 amps.
13. Insert the IntelliFlow
®
's power cord into a house
electrical outlet.
NOTICE
The IntelliFlow
requires a 120VAC, 60Hz, 15 amp ground-fault
®
protected receptacle.*
14. Install Leak Sensor
NOTICE
The IntelliFlow
will detect any current flow to the washing
®
machine when the washing machine is off. During startup or
at any time during troubleshooting, the IntelliFlow valve can be
reset to OFF condition by unplugging and reinstalling the leak
sensor.
Wall Box Unit (A2C-WB-M1)
®
15. Turn on both hot and cold water supply lines, and check for
leaks.
16. If there are no leaks, turn on the electrical power. Installation of
the IntelliFlow
connection.
®
®
's electrical outlet.
®
Finished
Wall
Mounting
Tabs (4)
*Ground Fault Interrupter – A GFI circuit is not required
for proper operation of the IntelliFlow
recommended as a safety device.
3
®
A2C-WB-M1 Wall Box Unit is now complete.
Trim Plate
Figure 5
(side view)
Trim Plate
Water supply connections
Figure 6
(front view)
16" on center – Typical
LISTED
3P47
U L
R
Trim Plate
Mounting
Slots (4)
Figure 7
(top view)
Wall Box
Drain connection
Wall
Studding
Drain
Drain
Knockout
®