Watts N170-M3 Serie Manual De Instrucciones

Watts N170-M3 Serie Manual De Instrucciones

Válvulas maestras de templado de agua caliente
Idiomas disponibles

Idiomas disponibles

ENGLISH INSTRUCTIONS
Series N170-M3 and LFN170-M3
Hot Water Master Tempering Valves
!
W ARNI NG
You are required to thoroughly read all installation instructions and
product safety information before beginning the installation of this prod-
uct. FAILURE TO COMPLY WITH PROPER INSTALLATION AND
MAINTENANCE INSTRUCTIONS COULD RESULT IN PRODUCT
FAILURE WHICH CAN CAUSE PROPERTY DAMAGE, PERSONAL
INJURY AND/OR DEATH. Watts is not responsible for damages result-
ing from improper installation and/or maintenance.
Local building or plumbing codes may require modifications to the
information provided. You are required to consult the local building and
plumbing codes prior to installation. If this information is not consistent
with local building or plumbing codes, the local codes should be fol-
lowed.
Installation Instructions
Installation should be in accordance with acceptable plumbing prac-
tices. Flush all pipes thoroughly before installation. Installation and field
adjustment are responsibility of the installer and shall be carried out per
following installation instructions.
1. Valves are to be installed as close to building inlet supply as possible
to prevent/minimize pressure fluctuations.
2. Valve body can be installed in multiple positions, see below. Make
sure that the union nuts and tailpieces are tightened securely if you
are using checkstops.
3. Connect inlets and outlet and check for leaks.
!
4.
CAUTION: When N170-M3 or LFN170-M3 supplies tempered
water to self-closing and/or solenoid valves, provide a shock absorb-
er on the discharge line.
5. Before use, check discharge temperature. Reset if necessary
Temperature Adjustment
1. Turn off recirculation pump (if one is in the system).
2. Open enough fixtures to meet the minimum flow requirement of the
valve.
3. Loosen the lock nut. Turn temperature adjustment screw clockwise
to decrease or counterclockwise to increase outlet temperature.
NOTE: Please allow valve temperature to stabilize in before making
your next adjustment. Watts recommends that a temperature gauge is
installed on the tempered line and be checked at least monthly under
normal flow conditions. The gauge must be installed at least 6 ft. away
from the tempering valve.
4. When desired temperature is set, tighten the lock nut. Turn recircu-
lation pump back on. Close open fixtures.
LFN170-M3
FRONT OUTLET
!
WA R N I N G
Watts Hot Water Master Tempering Valves cannot be used for
tempering water temperature at fixtures. Severe bodily injury (i.e.,
scalding or chilling) and/or death may result depending upon system
water pressure changes and/or supply water temperature changes.
ASSE standard 1016, 1069 or 1070 listed devices such as Watts
Series MMV, LFMMV, USG, LFUSG, L111 or LFL111 valves should be
used at fixtures to prevent possible injury.
The Watts Hot Water Tempering Valves are designed to be installed at
or near the boiler or water heater. They are not designed to compensate
for system pressure fluctuations and should not be used where ASSE
standard 1016, 1069 or 1070 devices are required. These Watts valves
should never be used to provide "anti-scald" or "anti-chill" service.
!
WA R N I N G
Need for Periodic Inspection: Periodic inspection by a licensed
contractor is recommended. Corrosive water conditions, tempera-
tures over 210°F, unauthorized adjustments or repair could render
the valve ineffective for service intended. Regular checking and
cleaning of the valves internal components and checkstops helps
to assure maximum life and proper product function. Frequency of
cleaning depends upon local water conditions.
IS-N170-M3
N170-M3 CSUT
BACK OUTLET
TOP OUTLET
Tabla de contenido
loading

Resumen de contenidos para Watts N170-M3 Serie

  • Página 5 LFUSG, L111 o LFL111, para evitar posibles lesiones. 2. Abra suficientes accesorios como para que pase el mínimo flujo Las válvulas de templado de agua caliente de Watts están diseñadas requerido para la válvula. para ser instaladas cerca de la caldera o del calentador de agua. No están diseñadas para compensar las fluctuaciones de presión del...
  • Página 6: Instalación Básica

    ASSE 1016, 1069 para las series N170-M3 o LFN170-M3 ó 1070, como las Watts L111, LFL111, USG, Tamaño de la válvula LFUSG, MMV, o LFMMV. 20 a 50 mm (¾ a 2 pulg.) 11 a 26,5 lpm (3 a 7 gpm) Especificaciones •...
  • Página 7: Sistema De Recirculación

    Sistema de recirculación 1 Al accesorio Serie Suministro de agua fría A MMV, USG-B, L111 o LFL111 , luego a los Termómetro accesorios Termostato para el agua WATTS CSA/ASME Válvula de temperatura Circulador Válvulas y liberación de presión Válvula retención esférica WATTS WATTS...
  • Página 8 USG, LFUSG, MMV o LFMMV. Limitaciones: Watts Regulator Co. (la “Compañía”) garantiza cada producto contra defectos en el material y mano de obra bajo condiciones normales de uso por un periodo de un año a partir de la fecha del envío original.