GB
Installation
Depending on the type of load, this corresponds to a power
output of 80% ≡ 168 W. A reduction of the installed load is
necessary if several dimmer are installed beside, or above,
one another, or if other heat sources lead to increased
heating up.
IMPORTANT
The installed load must be appropriately reduced since,
otherwise, there is a risk of destruction!
In intensely heated rooms, the maximum installed load must
be reduced in accordance with the diagram (see Fig. 2).
With an ambient temperature of 50 °C, the permissible power
output drops to 57% ≡ 120 W; with 60 °C, to 28% ≡ 59 W.