Menú Calibration (Calibración) - Woodward EGCP-2 Manual Del Usuario

Conjunto de control de generador y motor
Tabla de contenido
Manual SP26086
MENÚ CALIBRATION (CALIBRACIÓN)
Opción:
Intervalo:
Process In scale
Min: 0.5
Max: 2.0
Speed Bias offset
Min: -10.0
Max: 10.0
Min: -25.0
Volts Bias offset
Max: 25.0
Min: 0.5
PT Phase A scale
Max: 10.0
Min: 0.5
PT Phase B scale
Max: 10.0
PT Phase C scale
Min: 0.5
Max: 10.0
CT Phase A offset
Min: -90.0
Max: 90.0
CT Phase A scale
Min: 0.5
Max: 5.0
CT Phase B offset
Min: -90.0
Max: 90.0
Min: 0.5
CT Phase B scale
Max: 5.0
Min: -90.0
CT Phase C offset
Max: 90.0
CT Phase C scale
Min: 0.5
Max: 5.0
Bus PT scale
Min: 0.5
Max: 10.0
Synchronizer
Min: -1.0
Max: 1.0
Battery VCO Gain
Min: -0.1000
Max: 0.1000
Min: -900.0
Batt VCO offset
Max: 900.0
Min: -0.1000
Oil Press Gain
Max: 0.1000
Min: -900.0
Oil Press Offset
Max: 900.0
WaterTemp Gain
Min: -0.1000
Max: 0.1000
Water Temp
Min: -900.0
Max: 900.0
Offset
NetComm
Min: 0
Max: 50
Dropouts
False
Calibrated Unit
True
Woodward
Conjunto de control de generador y motor EGCP-2
Valor
predeterminado:
1.192
-0.42
0.05
2.6
2.6
2.6
0.0
1.90
0.0
1.90
0.0
1.90
2.6
0.00
0.0055
5.00
0.0174
-20.64
0.0399
-62.84
2
True
Valor según
Nota:
configuración:
No cambiar
143
Tabla de contenido
loading

Este manual también es adecuado para:

8406-1158406-116

Tabla de contenido