Manual SP26086
Opción:
Intervalo:
REMOTE FAULT6
Disabled
Warning
Visual Alarm
Audible Alarm
Soft Shutdown
Hard Shutdown
Min: 0.0
FAULT6 TIMER
Max: 30.0
Menú Engine Control (Control del motor)
Opción:
Intervalo:
PREGLOW TIME
Min: 0
Max: 1200
Min: 0
CRANK TIME
Max: 240
Min: 5
CRANK CUTOUT
Max: 10000
CRANK DELAY
Min: 1
Max: 240
CRANK
Min: 0
REPEATS
Max: 20
CRANK FAIL
Warning
Visual Alarm
Audible Alarm
IDLE SPEED
Min: 5
Max: 30000
IDLE TIME
Min: 1
Max: 240
Min: 0
COOLDOWN
Max: 2400
TIME
Min: 0
COOLDOWN
Max: 10000
LIMIT
ENGINE RUN
Min: 0
Max: 32000
TIME
MW HOURS
Min: 0.0
Max: 32000.0
OVERSPEED
Min: 5.0
Max: 30000.0
OVERSPEED
Disabled
Warning
ALARM
Visual Alarm
Audible Alarm
Soft Shutdown
Hard Shutdown
BATT VOLT HI
Min: 5.0
Max: 50.0
LMT
BATT VOLT HI
Disabled
Warning
ALM
Visual Alarm
Audible Alarm
Soft Shutdown
Hard Shutdown
BATT VOLT LO
Min: 5.0
Max: 50.0
LMT
Woodward
Conjunto de control de generador y motor EGCP-2
Valor
predeterminado:
Disabled
0.0 seconds
Valor
predeterminado:
5 sec
10 sec
550 RPM
30 sec
0
Warning
1200 RPM
10 sec
120 sec
20 kVA
0 Hours
0.0 MW Hrs
1980 RPM
Hard Shutdown
28.5 VOLTS
Warning
10.0 VOLTS
Valor según
Nota:
configuración:
Valor según
Nota:
configuración: