Conjunto de control de generador y motor EGCP-2
MENÚ REAL LOAD CONTROL (CONTROL DE CARGA
Opción:
Intervalo:
Droop
LOAD CONTROL
Normal
MODE
Soft Transfer
Min: 0.001
LOAD CTRL GAIN
Max: 100.0
Min: 0.1
LOADSHARE
Max2.0
GAIN
LOAD STABILITY
Min: 0.0
Max:20.0
LOAD
Min: 0.0
Max: 20.0
DERIVATIVE
LOAD CTRL
Min: 0.01
Max: 10.0
FILTER
Min: 0.0
BASE LOAD
Max: 30000.0
REFERENCE
Min: -10.0
UNLOAD TRIP
Max: 30000.0
Min: 0.0
LOAD DROOP
Max: 50.0
LOAD TIME
Min: 1.0
Max: 7200.0
UNLOAD TIME
Min: 1.0
Max: 7200.0
RAISE LOAD
Min: 0.01
Max: 100.0
RATE
Min: 0.01
LOWER LOAD
Max: 100.0
RATE
Min: 0.0
KW LOAD HIGH
Max: 30000.0
LIMIT
Disabled
KW HIGH LIMIT
Warning
ALARM
Visual Alarm
Audible Alarm
Min: 0.0
KW LOAD LOW
Max: 30000.0
LIMIT
KW LOW LIMIT
Disabled
ALARM
Warning
Visual Alarm
Audible Alarm
KVA SWITCH
Min: 0
LOW
Max: 30000
KVA SWITCH
Min: 0
Max: 30000
HIGH
138
REAL)
Valor
Valor según
predeterminado:
configuración:
Normal
0.01
0.72
2.00
0.20
1.0 Hz
50.0 kW
10 kW
5.0 %
10 seconds
10 seconds
2.00 %/second
2.00 %/second
30 kW
Warning
5 kW
Disabled
10 KVA
100 KVA
Manual SP26086
Nota:
Woodward