As it is a boiler room installation, we recommend using the cable connection to make the connections
between the boiler and the internet more reliable. They will need an Ethernet cable with an RJ45 connector.

Antenna.

Magnet connection base.
Place the magnet connection base with the antenna where appropriate. When possible, avoid the presence
of metal sheets around the antenna as the WiFi signal might be distorted.
WiFi upper view.
5.12. If our model has a plastic protection, it must be removed before starting it.
5.13. Due to the requirements of the EN303-5 standard, it is recommended mounting double wall piping for the
entire VAP range. This is also mandatory by the pipe manufacturer's directive if we go through the beams or
install gas outlet pipes outside the house. This is because the exhaust working temperatures of the aforesaid
range are between 65 and 140°C. The assembly of this pipe is to avoid condensation and excess dirt on it.
Mandatory: It will be made of a material resistant to the aggressive action of the combustion products, to
condensation and to constant temperatures of 300 °C. The material of the chimney will comply with the local
legislation for its application.
5.14. In cases of relative humidity in the environment higher than 60%, a drying system is highly recommended.
Check the indications of the regulation on boiler rooms.
5.15. Use flexible braided stainless steel hoses for the hydraulic connections or stainless steel dilators, respecting
the connection sections and always respecting the regulations for boiler rooms.
5.16. Seal the gas out pipe's joints with aluminium belt and silicone of high temperature (300 °C) and fix the pipe
with clamps so that it cannot be removed without tools nor move the heater / boiler.
In the case of safety distances and air inlet, as it is more than 70kW, the installation is governed by the
regulations EN 13384-1: 2003 + A2: 2008 for gas outlet, UNE-EN 303-5, UNE- EN 15053 and UNE-EN 1751
(Ventilation of buildings. Air terminal units. Aerodynamic tests of gates and valves.). In case of conflict between the
rules, the most restrictive one must be respected.
MATERIAL REQUIRED FOR INSALLATION.
SAFETY RULES FOR GASES OUTLET AND AIR INLET.
40
WiFi plan view with no metal objects around.
Drawing 8