Table 4
Tubing size (mm)
Exterior diameter
Wall thickness
Ø9.52
T0.8
Ø12.7
T0.8
Ø15.88
T1.0
Ø19.05
T1.0
Ø22.22
T1.0
Ø25.4
T1.0
Ø28.58
T1.0
Ø31.75
T1.1
Ø38.1
T1.35
After cutting the tube, be sure to remove all burrs and finish tubing ends to the
correct surface. (The same must be done for branch tubes (purchased separately).)
When bending tubes, be sure the bend radius is at least 4 times the outer diameter
of the tube.
When cutting or bending tubes, be careful not to cause any pinching or blockage of
the tube.
• Prevent foreign substances such as dirt or water from entering the tube by
sealing the end of the tubes with either a cap or with tape.
Otherwise, this can damage the devices and result in malfunction.
3-3. Connecting the refrigerant tubing
1. Remove the tube fastening rubber on the gas and liquid tubes from the pipe connection panel.
2. Connect the tubes and perform brazing.
3. Reattach the gas tube, liquid tube fastening panel, and fastening rubber as they were originally.
Type
O
1/2 H or H
EN - 15
Tube connection panel
Liquid tube fastening rubber
Gas tube fastening rubber
Liquid tube
Gas tube
Fig. 15