Start-Up Instructions; Shut-Down Instructions - L.B.White Guardian AB250 Manual Del Usuario E Instrucciones

Ocultar thumbs Ver también para Guardian AB250:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Start-Up Instructions

Follow steps 1 - 8 on initial start-up after
heater installation by a qualified gas heater
service person. For normal start-up, simply
turn thermostat above room temperature. The
heater will start.
1. Open all manual fuel supply valves and
check for gas leaks using approved certified
leak detectors.
2. The gas control valve incorporates a
manual gas shut off feature. Position the
indicator on the shut off knob to PILOT.
3. Fully depress the red pilot button located on
the control valve while applying flame to the
pilot light orifice. See Fig. 12.
4. Keep the button depressed for about 30
seconds to allow the thermocouple to warm
up so the pilot stays lit after you release
the pilot button. On new installations it may
take about a minute for the gas to purge out
any air in the pilot line before the pilot lights.
5. Position the knob to ON.
6. Connect the heater's electrical cord to an
approved electrical outlet.
FIG. 12
PILOT
BUTTON
7. Set the thermostat above room tempera-
ture. The heater will light. Reset thermostat
to desired room temperature.
8. Do not exceed input rating stamped on
nameplate of appliance, or manufacturer's
recommended burner orifice pressure for
size orifice(s) used.
Guardian LP or Natural Gas Heater

Shut-Down Instructions

If the heater is to be shut-down for cleaning, maintenance
or repair, follow steps 1-4. Otherwise, simply turn thermo-
stat to OFF or no heat for standard shut down.
1. Close all manual fuel supply valves.
2. With the heater lit, allow heater to burn off excess fuel
in gas supply hose.
3. Turn thermostat to off or no heat position.
4. Disconnect the heater from the electrical supply.
KNOB
Owner's Manual • Guardian
15