PURPOSE OF THE MACHINE

The cassette convector fan is a terminal appliance that treats the air in a room both in the summer and winter . The
appliance must be installed on the ceiling . It is equipped with a very pleasantly designed grille .

AVAILABLE VERSIONS

This new series of cassette type convector fans is available in the version
with 2 pipes in 4 sizes and 3.93 to 10.64 kW nominal cooling capacity ratings
and in the version with 4 pipes (-4T) in 2 sizes with 2.88 to 5.18 kW nominal
cooling capacity ratings .

DESCRIPTION OF THE MAIN COMPONENTS

The unit consists of a module or main structure containing a finned exchanger, the ventilating unit formed by a
three speed motor and a centrifugal axial fan, a tray to collect the condensation equipped with a pump to drain
this off .
Applied externally houses the electrical box.
The unit also has a grille made of thermoplastic material and formed by a frame which houses the filter and air
flow directing fins plus an intake grille: the air flow directing fins are installed on each side of the grille and can be
positioned by remote control. The intake grille is fixed in a practical way that allows it to be easily inspected for
servicing and filter cleaning operations.
GENERAL VIEW OF THE UNIT
The drawings below highlight the fundamental parts of the unit .
It is reported:
Unit: Includes battery, fan assembly, pump and electrical box
Panel: Plastic material includes frame, grille and air filter, air orientation vents and signal receiver from the remote
control .
Brackets: arranged on four corners of the unit serve for the suspension and fastening of the unit.
Condensate discharge pipe: for the evacuation of the condensate that is formed in cold operation .
Air vent valves: placed on the upper manifold allows the evacuation of the air in the system .
Exhaust Valve: present on the lower manifold allows water drainage from the plant.
Hole for connecting with auxiliary basin: bring the water on the auxiliary basin to the main basin and then evacuate
it from the pump .
brackets
Condensate
exhaust
pipe
Air vent valve
discharge valve
Hole for connecting
auxiliary basin

GENERAL SPECIFICATIONS

Unit
Panel
brackets
Hole for connecting auxiliary basin
UNITA'
1500
400-4
750-4
Unit
Panel
brackets
Air vent valve
discharge valve
VERSIONE
400
600
2 TUBI
850
4 TUBI
Fig . 1
Condensate
exhaust pipe
brackets
5