SELF TEST SYSTEM

The diagnostic system and status clock, which will operate each camera function in turn for two
seconds, is activated either locally, by switching the DIP switch SW1
switch 1 ON and immediately OFF, or remotely from the keyboard. When testing the system
locally, before initiating the diagnostic system and status clock ensure that the cable LED is on.
(Either flashing or continuously) If not, this indicates that either the power is not connected to the
p.c.b. or that there is a major p.c.b. error which will have to be rectified.
The ERROR LED flashes at a two second rate during self test. If the CABLE LED fails to
extinguish, then the unit is unable to self tune and should be returned to the supplier for repair.
CAMERA MOVES RIGHT
CAMERA MOVES LEFT
CAMERA MOVES DOWN
CAMERA MOVES UP
AUXILIARY WIPE
AUXILIARY WASH
AUXILIARY ILLUMINATORS
LENS ZOOM IN
LENS ZOOM OUT
LENS FOCUS NEAR
LENS FOCUS FAR
AUTO IRIS OVERRIDE OPEN
AUTO IRIS OVERRIDE CLOSE
ALARM OUTPUT
N.B.
If the receiver is connected to a dtx1000/8AL or a dtx1000/16AL telemetry transmitter, the Alarm
Output self test will generate an alarm condition at the dtx1000 keyboard at the completion of the
test, in order to test continuity of the alarm wiring.
The pin-outs listed above as test points refer to connectors shown in the drx 400dc p.c.b. layout on
sheet .6
drx 400d.c. Installation Manual
FUNCTION
TEST POINT
J13-1 and 2
J13-1 and 2
J13-7 and 8
J13-7 and 8
J8-9
J8-6
J8-3
J3-7
J3-7
J3-5
J3-5
J3-4
J3-4
J6-1 and 2
Page. 10