Eaton Metalux WaveStream Instrucciones De Instalación página 2

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Installation Instructions – Luminaire WaveStream
3.
Install the luminaire into the ceiling T-grid system.
Ensure that luminaire sets snuggly in T-grid system
(Figure 2.). Ensure that all luminaires in an area are
oriented in the same direction.
4.
When required, attach EQ Clips to luminaire end plate
with supplied screws to secure luminaire to T-grid
system (Figure 3.). Take care to not over-torque and
strip screws.
5.
Remove electrical access plate and remove necessary
knockouts from access plate for attachment of electrical
supply cable (Figure 4. and Figure 5.).
6.
Remove two screws in Electrical Enclosure and review
driver label for electrical ratings and proper wiring of
the LED driver. Replace Electrical Enclosure and secure
with the two screws previously removed.
Standard Access Plate Installation
Grounding conductor (if insulated) to be stripped min. 1".
Insert end of wire into small hole. Wrap wire under and
around head of screw counter-clockwise (Figure 4.). Tighten
screw.
Flex Installation
Step 1: To insert access plate, rotate until leading end is
inside the wireway (Figure 5.).
Step 2: Fold into horizontal position and slide forward into
locking position.
7 .
Make necessary wiring connections to driver AC line
input and optional DALI or 0-10Vdimming circuits. See
Wiring Diagrams
8.
Replace electrical access plate and snap securely into
place. If required, install optional screw to lock the
access plate closed.
BLACK OR BROWN = LINE
WHITE OR BLUE = NEUTRAL
GRN OR GRN/YLW = GROUND
PURPLE = DIM +
GREY = DIM –
BLACK OR BROWN = LINE
WHITE OR BLUE = NEUTRAL
GRN OR GRN/YLW = GROUND
PURPLE = DALI
GREY = DALI
BLACK OR BROWN = LINE 1
BLUE OR ORANGE = LINE 2
WHITE OR BLUE = NEUTRAL
GRN OR GRN/YLW = GROUND
Wiring Diagrams
2
RED = LED +
BLUE = LED –
0-10V DIM
DRIVER
RED = LED +
BLUE = LED –
DALI
DRIVER
RED = LED +
BLUE = LED –
STEP DIM
DRIVER
Installation Instructions – Luminaire WaveStream
Electrical
Enclosure
Figure 2.
Install in Ceiling T-Grid System
Figure 3.
LED
LOAD
Figure 4.
Step 1
LED
LOAD
Figure 5.
LED
LOAD
0590AWSIS
ADF140666
EQ Clip Installed
Access Plate
Leading End
Step 2
Tabla de contenido
loading

Tabla de contenido