2.1 Pin assignment: Power supply
Socket: Type NTSD−GD−9−M12−5POL−RK (B−coded)
Power
4
1
5
2.2 Example of connection with electrical isolation of
electronics and load voltage
1
Power unit for load
voltage (valves and
outputs)
2
Device for isolation
monitoring
3
Load voltage can be
switched off
separately and
external fuses
4
Power unit for
operating voltage
(electronics and
sensors)
Festo CPASC−DN 0412a English
1: 24 V DC electronics (and CP sensors)
2: 24 V DC valves (and CP outputs)
3
3: 0 V electronics (and CP sensors)
2
4: 0 V valves (and CP outputs)
5: FE (functional earth)
1
24 V
4
24 V
2
3
0 V
0 V
2
3 4 1 2 5
17