Quick Parameter Reference, Faults and Alarms
Fault / Alarm
F0076
This fault indicates the motor presents
Output Phase
phase loss, imbalanced phase current
Current Fault
or is disconnected.
F0078
Overtemperature fault measured on the
Motor
motor temperature sensor (Triple PTC)
overtemperature
via analog input AIx or digital input DIx.
F0080
Fault related to the supervision
CPU fault
algorithm of the inverter main CPU.
(Watchdog)
F0084
Fault related to the automatic
Auto-diagnosis
identification algorithm of the inverter
fault
hardware and Plug-In module.
F0091
External fault via DIx ("No External
External fault
Fault" option in P0263 to P0270).
F0182
Pulse feedback circuit fault of the
Pulse feedback
output voltage.
fault
Note: it may be turned off in P0397.
F0228
Serial communication timeout.
Telegram reception
It indicates the equipment stopped
timeout
receiving valid serial telegrams for a
period longer than the setting in P0314.
F0700
No communication with remote HMI,
Remote HMI
but there is speed command or
communication fault
reference for this source.
F0711
The upload or the SoftPLC application
The upload of
failed.
the SoftPLC
application failed
F0761
Fault that indicates the process
Low Level of the
variation of the main PID controller has
Process Variable
a low value.
of the Main PID
Controller
F0763
Fault that indicates the process
High Level in the
variation of the main PID controller has
Process Variable
a high value.
of the Main PID
Controller
F0767
Fault that indicates the dry pump
Dry Pump
condition was detected for the pump
Detected
driven by the CFW501 frequency
inverter.
24 | CFW501
Description
Possible Causes
Motor wiring or connection error.
Loss of motor connection with the drive or broken wire.
Overload on the motor shaft.
Load cycle is too high (high number of starts and
stops per minute).
High ambient temperature around the motor.
Poor contact or short circuit (3.9 kΩ < R
Motor thermistor not installed.
Motor shaft is stuck.
Electric noise.
Inverter firmware fault.
Poor contact in the connection between the main
control and the power pack.
Hardware not compatible with the firmware version.
Defect on the internal circuits of the inverter.
Wiring on DI1 to DI8 inputs are open or have poor
contact.
Hardware identification fault; compare P0295 and
P0296 to the inverter identification label.
Inverter internal circuits fault.
Check network installation, broken cable or fault/
poor contact on the connections with the network,
grounding.
Ensure the master always sends telegrams to the
equipment in a time shorter than the setting in P0314.
Disable this function in P0314.
Check if the communication interface with the HMI is
properly configured in parameter P0312.
HMI cable disconnected.
Fault in the HVAC plug-in connection.
Fault in the communication between the HVAC plug-in
board and the main control board.
Fault in the SoftPLC boot by the CPU.
Parameter P1030 is programmed for 2 and the value
of the process variation of the main PID controller
remained below the value programmed in P1031 for
the time programmed in P1032.
Parameter P1030 is programmed for 2 and the value
of the process variation of the main PID controller
remained above the value programmed in P1033 for
the time programmed in P1034.
Parameter P1042 is programmed for 2 and the pump
driven by the CFW501 frequency inverter is running
with speed above the speed programmed in P1043
and the motor torque remained below the value
programmed in P1044 for the time programmed
in P1045.
< (100 Ω).