Installing the DH-485
Communication Cable
Personal
Computer
to serial port
to
1784-PCMK
card in
1747-PIC
PCMCIA
Interface
slot
Converter
1784-PCM4
Cable
Powering the Link Coupler
1
®
SLC
Link Coupler
(Catalog Number 1747-AIC)
DH-485 Link
to USB port
USB (DF1)
1747-UIC
USB
OK
DH485
USB to DH485
INTERFACE CONVERTER
Interface
CAT
SER
FRN
1747-UIC
A
X.X
C
R
US
LISTED IND. CONT. EQ. FOR HAZ.
LOC. A196,
OPERATING TEMP CODE TAG
CLASS 1 GROUPS A, B, C, AND D, DIV. 2
RS485 (DH485)
Converter
SW
Mfg
XXXX
N223
RS232 (DH485)
1747-C13
Cable
158 mm
(6.22 in)
SLC 500
ALLEN-BRADLEY
1747-C10
Cable
1747-AIC
Link Coupler
Publication 1747-UM011, SLC 500 Modular Hardware Style User
Manual, contains complete instructions and guidelines for DH-485
link planning.
In normal operation with the programmable controller connected to
the link coupler, the processor powers both the link coupler and the
peripheral device (DTAM, PIC, HHT) — if connected — through the
1747-C11 cable. No external power supply is required.
If you do not connect the processor to the link coupler, use a Class 2
24V dc power supply to power the link coupler and peripheral
device.
ATTENTION
!
500 Programmable Controller Isolated
Belden #3106A or #9642
DH-485
Peripheral
1747-C11
CPU
Cable
Power
Always connect the CHS GND (chassis ground)
terminal to the nearest earth ground. This connection
must be made whether or not an external 24V dc
power supply is used.
Installation Instructions
Use Belden#3106
or #9842 shielded,
SLC 500 Fixed
twisted-pair cable.
Controller
Daisy-chain cable
segments together.
Total length of
cable segments
SLC 500 Modular
cannot exceed
Controller
1219m (4000 ft).
Publication 1747-IN062A-MU-P - April 2003