Terminal
60
61
62
63
64
65
70
71
72
73
74
75
76
77
78
Y
#
Aux logic= 0 - MONOSTABLE RADIO CHANNEL output.
Contact stays closed for 1s when radio channel is activated.
Aux logic= 1 - SCA GATE OPEN LIGHToutput.
Contact stays closed during opening and with leaf open, intermittent during closing, open with leaf closed.
Aux logic= 2 - COURTESY LIGHT command output.
Contact stays on for 90 seconds after the last operation.
Aux logic= 3 - ZONE LIGHT command output.
Contact stays closed for the full duration of operation.
Aux logic= 4 - STAIR LIGHT output.
Contact stays closed for 1 second at start of operation.
Aux logic= 5 - GATE OPEN ALARM output.
Contact stays closed if the leaf stays open for double the set TCA time.
Aux logic= 6 - FLASHING LIGHT output.
Contact stays closed while leaves are operating.
Aux logic= 7 - SOLENOID LATCH output.
Contact stays closed for 2 seconds each time gate is opened or closed.
Aux logic= 8 - MAGNETIC LOCK output.
Contact stays closed when gate is closed and while it is closing.
Aux logic= 9 - MAINTENANCE output.
Contact stays closed once the value set for the Maintenance parameter is reached, to report that maintenance is required.
Aux logic= 10 - FLASHING LIGHT AND MAINTENANCE output.
Contact stays closed while leaves are operating. If the value set for the Maintenance parameter is reached, once the gate has finished moving and the leaf is closed, the contact closes
for 10 sec. and opens for 5 sec. 4 times to report that maintenance is required.
Aux Logic= 11 – Not used
Aux Logic= 12 – Antitampering output : the contact closes if the gate is moved from the closing limit switch without the motor being supplied.
The contact opens after a remote or button command.
Aux logics= 13 - GATE STATUS output
Contact stays closed while gate is closed.
AUX logics= 14 - BISTABLE RADIO CHANNEL output
The contact changes status (open-closed) when the radio channel is activated
AUX logics= 15 - TIMED RADIO CHANNEL output
The contact remains closed for a programmable length of time when the radio channel is activated (output time)
If, during this time, the button is pressed again, counting starts all over again.
IC logic= 0 - Input configured as Start E. Operation according to STEP-BY-STEP MOV. logic. External start for traffic light control.
IC logic= 1 - Input configured as Start I. Operation according to STEP-BY-STEP MOV. logic. Internal start for traffic light control.
IC logic= 2 - Input configured as Open.
The command causes the leaves to open. If the input stays closed, the leaves stay open until the contact is opened. When the contact is open, the automated device closes following
the TCA time, where activated.
IC logic= 3 - Input configured as Closed.
The command causes the leaves to close.
IC logic= 4 - Input configured as Ped.
The command causes the leaf to open to the pedestrian (partial) opening position. Operation according to STEP-BY-STEP. logic
IC logic= 5 - Input configured as Timer.
Operation same as open except closing is guaranteed even after a mains power outage.
IC logic= 6 - Input configured as Timer Ped.
The command causes the leaf to open to the pedestrian (partial) opening position. If the input stays closed, the leaf stays open until the contact is opened. If the input stays closed and a Start E,
Start I or Open command is activated, a complete opening-closing cycle is performed before returning to the pedestrian opening position. Closing is guaranteed even after a mains power outage.
SAFE logic= 0 - Input configured as Phot (photocell) non tested (*) (fig.D, ref.1).
Enables connection of devices not equipped with supplementary test contacts. When beam is broken, photocells are active during both opening and closing. When beam is broken
during closing, movement is reversed only once the photocell is cleared. If not used, leave jumper inserted.
SAFE logic= 1 - Input configured as Phot test (tested photocell). (fig.D, ref.2).
Switches photocell testing on at start of operation. When beam is broken, photocells are active during both opening and closing. When beam is broken during closing, movement is
reversed only once the photocell is cleared.
SAFE logic= 2 - Input configured as Phot op (photocell active during opening only) non tested (*) (fig.D, ref.1).
Enables connection of devices not equipped with supplementary test contacts. In the event beam is broken, photocell operation is disabled during closing. During opening, stops
motion for as long as the photocell beam stays broken. If not used, leave jumper inserted.
SAFE logic= 3 - Input configured as Phot op test (tested photocell active during opening only (figD, ref.2).
Switches photocell testing on at start of operation. In the event beam is broken, photocell operation is disabled during closing. During opening, stops motion for as long as the photocell beam stays broken.
SAFE logic= 4 - Input configured as Phot cl (photocell active during closing only) non tested (*) (fig.D, ref.1).
Enables connection of devices not equipped with supplementary test contacts. In the event beam is broken, photocell operation is disabled during opening. During closing, move-
ment is reversed immediately. If not used, leave jumper inserted.
24 - LEO B CBB DL2 3 230 L02-LEO B CBB DL2 3 120 F02-LEO B CBB DL2 3 120 F02 PHOT USA16 - LEO B CBB DL2 3 230 SV
INSTALLATION MANUAL
Definition
Common
IC 1 and IC 2 inputs common
Configurable command input 1 (N.O.) - Default START E.
IC 1
START E / START I / OPEN / CLOSE / PED / TIMER / TIMER PED
Refer to the "Command input configuration" table.
Configurable command input 2 (N.O.) - Default PED.
IC 2
START E / START I / OPEN / CLOSE / PED / TIMER / TIMER PED
Refer to the "Command input configuration" table.
Common
IC 3 and IC 4 inputs common
Configurable command input 3 (N.O.) - Default OPEN.
IC 3
START E / START I / OPEN / CLOSE / PED / TIMER / TIMER PED
Refer to the "Command input configuration" table.
Configurable command input 4 (N.O.) - Default CLOSE.
IC 4
START E / START I / OPEN / CLOSE / PED / TIMER / TIMER PED
Refer to the "Command input configuration" table.
Common
STOP, SAFE 1 and SAFE 2 inputs common
The command stops movement. (N.C.)
STOP
If not used, leave jumper inserted.
Configurable safety input 1 (N.C.) - Default PHOT.
PHOT / PHOT TEST / PHOT OP / PHOT OP TEST / PHOT CL / PHOT CL TEST / BAR / BAR TEST / BAR 8K2 / BAR OP / BAR OP TEST /
SAFE 1
BAR 8K2 OP/ BAR CL / BAR CL TEST / BAR 8K2 CL
Refer to the "Safety input configuration" table.
FAULT 1
Test input for safety devices connected to SAFE 1.
Configurable safety input 2 (N.C.) - Default BAR.
PHOT / PHOT TEST / PHOT OP / PHOT OP TEST / PHOT CL / PHOT CL TEST / BAR / BAR TEST / BAR 8K2 / BAR OP / BAR OP TEST /
SAFE 2
BAR 8K2 OP/ BAR CL / BAR CL TEST / BAR 8K2 CL
Refer to the "Safety input configuration" table.
FAULT 2
Test input for safety devices connected to SAFE 2.
Common
SAFE 3 input common
Configurable safety input 3 (N.C.) - Default PHOT OP.
SAFE 3
PHOT / PHOT TEST / PHOT OP / PHOT OP TEST / PHOT CL / PHOT CL TEST / BAR / BAR TEST / BAR OP / BAR OP TEST / BAR CL / BAR CL TEST.
Refer to the "Safety input configuration" table.
FAULT 3
Test input for safety devices connected to SAFE 3.
Antenna input.
ANTENNA
Use an antenna tuned to 433MHz. Use RG58 coax cable to connect the Antenna and Receiver. Metal bodies close to the an-
tenna can interfere with radio reception. If the transmitter's range is limited, move the antenna to a more suitable position.
SHIELD
AUX output configuration
Command input configuration
Safety input configuration