LIST OF ACCESSORIES THAT ALLOW THE
CONFIGURATIONS INDICATED ARE SUPPLIED
ON REQUEST:
– Separate flue kit code 8089905
– 90° elbow MF code 8077410 (6 pz.)
– 90° insulated elbow MF code 8077408
– 90° elbow MF with take-off points
code 8077407
– Extension L. 1000 code 8077309 (6 pz.)
– Insulated extension L. 1000 code 8077306
– Extension L. 500 code 8077308 (6 pz.)
– Outlet terminal code 8089501
– Int.-est. ring kit code 8091500
– Inlet terminal code 8089500
– 45° elbow MF code 8077411 (6 pz.)
– Condensation outlet L. 135 code 8092800
– Doubler fitting code 8091400
– Tile with articulated joint code 8091300
– Roof outlet terminal L. 1390 code 8091201
– Tee condensation outlet code 8093300
WARNING:
- The outlet and intake ducts of type C52 cannot
be located on opposite walls.
- Types B22-B52 refer to the outlets of one
discharge duct only because suction is from
the environment.
2.9
POSITIONING OF OUTLET
TERMINALS
The outlet terminals for forced draught
TABLE 2
Siting of terminal
A - below openable window
B - below ventilation opening
C - below eaves
D - below balcony (1)
E - from adjacent window
F - from adjacent ventilation opening
G - from horizontal or vertical soil or drain pipes (2)
H - from corner of building
I - from recess in building
L - from ground level or other treadable surface
M - between two terminals set vertically
N - between two terminals set horizontally
O - from a surface facing without
openings or terminals
P - as above but with openings and terminals
1) Terminals below a practicable balcony must be located in such a way that the total path of the smoke from its outlet point from the terminal to its outlet
point from the external perimeter of the balcony, including the height of possible railings, is not less than 2000 mm.(?)
2) When siting terminals, where materials that may be subject to the action of the combustion products are present in the vicinity, e.g., eaves, gutters and
downspouts painted or made of plastic material, projecting timberwork, etc., distances of not less than 1500 mm must be adopted, unless adequate shiel-
ding is provided to guard these materials.
C42
systems may be located on the outer
walls of the building.
Table 2 shows approximate, non-binding
Appliances from 7 to 35 kW
(distances in mm)
600
600
300
300
400
600
300
300
300
2500
1500
1000
2000
3000
min. 700
C32
C52
B52
C82
B22
C 12
B52
minimum distances to be met for a buil-
ding of the type shown in fig. 6.
IT
ES
PT
GB
max 0,5 m
Fig. 5
Fig. 6
41