CORRESPONDANCES
DES BORNES
S8910U
50E/F47
TERRE (BRÛLEUR)
TERRE
24 V (TERRE)
TR
VANNE (TERRE)
MV (PRÈS DE TR)
24 V
TH
VANNE
MV
L2
—
L1
4
L
HSI
—
4
HSI
ALL.
CAPTEUR
FP
1
ALIMENTATION. PLACER SI NÉCESSAIRE UN DISPOSITIF DE COUPURE
ET UNE PROTECTION CONTRE LES SURCHARGES VEILLER À NE PAS
INVERSER L1 ET L2.
2
EMPLACEMENT DU LIMITEUR AUXILIAIRE.
3
RETIRER LE CONNECTEUR RAPIDE CAVALIER DU S8910U. COUPER LE FIL CAVALIER AU NIVEAU DE LA CARTE DE CIRCUIT ET LE JETER.
4
UTILISER LE BOUCHON D'ADAPTATEUR AVEC LES FILS NOIR ET ORANGE (FOURNI).
5
COUPER LE CONNECTEUR RAPIDE DE 3/16 PO DU FIL ET LE REMPLACER PAR LE CONNECTEUR RAPIDE 1/4 PO (FOURNI).
6
COUPER LE CONNECTEUR RAPIDE DE 3/16 PO DU FIL ET LE REMPLACER PAR LE CONNECTEUR RAPIDE 3/16 PO (FOURNI).
Fig. 2. Raccordement typique lorsque le modèle S8910U remplace le modèle White-Rodgers 50E/F47.
CONTRÔLEUR D'ALLUMAGE PAR INCANDESCENCE S8910U
S8910U Hot Surface Ignition
WARNING
Input Voltages = 120 & 24 VAC, 60 Hz
HSI = 120V, 5A max.
Valve = 24V, 2A max.
Explosion Hazard. Can cause
Total 24V Load = 0.4 + valve load
serious injury or death.
U.S. Patent 8,085,521
Disconnect power before ser-
Prepurge Time = 32 Sec.
vicing. This device can mal-
Igniter Warm Up Time = See Inst. Sh. 34-00008
function if it gets wet. Never
Ignition Trial Time - See Selection Tab
try to use a device that has
Number of Trials - See Selection Tab
been wet -- replace it.
Between Trial Time - 96 Sec.
See
LED
States
TERRE DU
5
BRÛLEUR
MV
CONTRÔLEUR
GAZ COMBINÉ
MV
THERMOSTAT
OU CONTRÔLEUR
11
Golden Valley, MN 55422
Assembled in Mexico
Selection Tab
LED States
ON
Trial count
Control Status
Color Pattern
OFF
= 1 try (default)
Device damaged- Red
Steady
ON
Trial count
replace control
OFF
= 3 tries
Ignition lockout
Red
Blink
ON
Trial for ign. period
Normal operation Green Steady
OFF
= 4 seconds (default)
Weak flame signal Green Blink
ON
Trial for ign. period
See Instruction Sheet 34-00008
OFF
= 7 seconds
for additional states
1
2
3
4
32304204-001 Rev. A
120 VAC
120 VAC
NOTE: ALWAYS apply
See
NEUTRAL
HOT
this control as instructed
Instructions
in Instruction Sheet
for
34-00008
Single/Dual
SYSTEM SETUP
Rod
Applications
6
4
ORANGE
NOIR
ADAPTATEUR
LIMITEUR
2
S8910U3000
®
C
US
AUTO
IGNITION
SYSTEMS
ANSI Z21.20
CAPTEUR
DE FLAMME
3
ALLUMEUR PAR
INCANDESCENCE
4
L1
(SOUS TENSION)
L2
1
MF8528
34-00008EFS—01