Hitachi CSNET WEB Manual De Instalación Y Funcionamiento página 14

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 19
CSNET WEB
Installation & Operation Manual
Attention:
Very important:
The IP, Mask and Gateway parameters were already cofigured when you used the CD-ROM. In any case, they may be
modified again as shown below.
Remember that, once they have been modified, you will be disconnected and you wil have to reconnect by changing the
previous IP to the new address.
Note
You must always refer to the person in charge of the computer system CSNET WEB connects to concerning this configuration.
Once you have changed the IP configuration, you must restore the PC's configuration to ensure that it is in the same network
as CSNET WEB and thus reconnect with the new IP.
It is advisable to change it only after all other configurations have been completed.
b. Change password
The Change button beside Password setting opens the
Change password panel.
To change your password:
- Enter the installer password. (The default factory
password is "Installer").
- Enter the new password.
- Repeat the new password to confirm it.
- Click the "Change" button to validate the changes and
return to system configuration window.
Note
Only Installer password may be changed for CSNET WEB
Server. User password will no longer be used for CSNET
WEB Server."
c. Installation Name:
Enter a name that identifies the installation or the
building. Click 'Change' to update it.
d. Auto Configuration:
This step is not required if power is applied to CSNET
WEB after all the refrigerant circuits that you want to
control have been activated. If this is not the case, it is
advisable to activate auto-configuration. The following
three options are available:
- Keep All: Keeps all the machines that were previously
registered (although they weren't found), and adds the
new ones.
- Delete Not Found: Deletes all the machines that were
previously registered (unless they were found), and
adds the new ones.
- Delete All: Deletes all the machines that were
previously registered and adds the ones it has found.
Select the option and click Start to start unit recognition.
e. Time & Time Zone
Enter the date and time. Always respect the indicated
format: "yyyy/mm/dd hh:mm"
Select the geographical area nearest the installation.
Click Change to update CSNET WEB time and time zone.
f. Ethernet Gateway IP & Ethernet Gateway MAC.
You can change the IP and MAC values of your Gateway
here by clicking the button Change.
Page 12
PMML0163A-rev.0 - 03/2008
g. Config. Backup / Restore.
Clicking on Backup button you can save your system
configuration. If you want ro restore it, you must click con
Restore button.
h. BMS Enable
For enable BMS, select BMS enabled box, and click
Change to apply the setting.

Hide quick links:

Tabla de contenido
loading

Tabla de contenido