Easy Maintenance Function - Mitsubishi Electric Mr.SLIM PKA-RP HAL Manual De Instalación

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 70

8. Easy maintenance function

Maintenance data, such as the indoor/outdoor unit's heat exchanger temperature and compressor operation current can be displayed with "Smooth maintenance".
* This cannot be executed during test operation.
* Depending on the combination with the outdoor unit, this may not be supported by some models.
1
Check menu
Error history
Refrigerant volume check
Refrigerant leak check
Smooth maintenance
Request code
Service menu:
Cursor
F1
F2
2
Smooth maintenance
Ref.address
Stable mode
Begin:
Cursor
Smooth maintenance
Ref.address
Stable mode
Stabilization→Collecting
Exit:
3
Smooth maintenance
Ref. address
COMP. current
COMP. run time
COMP. On / Off
COMP. frequency
Return:
Page
Smooth maintenance
Ref.address
Sub cool
OU TH4 temp.
OU TH6 temp.
OU TH7 temp.
Return:
Page
Smooth maintenance
Ref.address
IU air temp.
IU HEX temp.
IU filter time
Return:
Page
18
F3
F4
Cool
/ Heat/ Normal
Address
Cool
/ Heat/ Normal
Cool
A
Hr
times
Hz
Cool
Cool
Hr
• Select "Service" from the Main menu, and press the [SELECT] button.
• Select "Check" with the [F1] or [F2] button, and press the [SELECT] button.
• Select "Smooth maintenance" with the [F1] or [F2] button, and press the
[SELECT] button.
Select each item.
• Select the item to be changed with the [F1] or [F2] button.
• Select the required setting with the [F3] or [F4] button.
"Ref. address" setting .......... "0" - "15"
"Stable mode" setting........... "Cool" / "Heat" / "Normal"
• Press the [SELECT] button, fixed operation will start.
* Stable mode will take approx. 20 minutes.
The operation data will appear.
The Compressor-Accumulated operating (COMP. run) time is 10-hour unit, and the
Compressor-Number of operation times (COMP. On/Off) is a 100-time unit (fractions
discarded)
Navigating through the screens
• To go back to the Main menu ....................[MENU] button
• To return to the previous screen .......... [RETURN] button