Adjustment of pressure at burner
Since this unit has flame modulation, there are two fixed pressure values: the minimum
and maximum, which must be those given in the technical data table according to the
type of gas.
Connect a suitable pressure gauge to pressure point "B" downstream of the gas
valve
Disconnect the pressure compensation tube "H" and remove the protection cap
"D", undoing screw "A".
Operate the boiler in TEST mode.
Set the heating power to 100.
Adjust the max. pressure with screw "G", clockwise to increase it and anticlockwise
to decrease it
Disconnect one of the two fastons from modureg "C" on the gas valve.
Adjust the min. pressure with screw "E", clockwise to decrease it and anticlockwise
to increase it.
Reconnect the faston detached from the modureg on the gas valve.
Check that the maximum pressure has not changed.
Reconnect the pressure compensation tube "H".
Refit the protection cap "D".
To end the TEST mode, repeat the activation sequence or wait 15 minutes.
After checking or adjusting the pressure, make sure to seal the adjust-
A
ment screw with paint or a specific seal.
E
G
C
D
fig. 26 - Gas valve
A - Protection cap screw
B - Downstream pressure point
C - Modureg cable
D - Protection cap
E - Min. pressure adjustment
G - Max. pressure adjustment
H - Compensation tube
Heating power adjustment
To adjust the heating power, switch the boiler to TEST mode (see sec. 3.1). Press the
heating buttons fig. 1 (details 3 and 4 - ) to increase or decrease the power (min. = 00 -
max. = 100). Press the RESET button within 5 seconds and the max. power will remain
that just set. Exit TEST mode (see sec. 3.1).
Lighting power adjustment
To adjust the lighting power, switch the boiler to TEST mode (see sec. 3.1). Press the
DHW buttons (details 1 and 2 - fig. 1) to increase or decrease the power (min. = 00 - max.
= 60). Press the RESET button within 5 seconds and the lighting power will remain that
just set. Exit TEST mode (see sec. 3.1).
Service menu
The card is equipped with two Menus: one for configuration and the other for Service.
The configuration Menu is accessed by pressing the DHW buttons together for 10 sec-
onds. 2 parameters, modifiable only from card, are available.
Remote control
Card
Description of transparent parameters
NO
P01
Exchanger type selection
NO
P02
Boiler shell Warm-up activation temperature 0-80°C
If replacing the card, always set the parameter P01 to 0=Copper.
To exit the configuration Menu, press the DHW buttons together for 10 seconds.
The card Service Menu is accessed by pressing the Reset button for 10 seconds. Press
the Heating buttons to select "tS", "In", "Hi" or "rE". tS" means Transparent Parameters
Menu, "In" Information Menu, "Hi" History Menu, and "rE" History Menu Reset. After se-
lecting the Menu, press the Reset button to access it.
23
EN
H
H
C
D
Range
0=Copper
1=Cast iron
cod. 3541B530 - 01/2012 (Rev. 00)
"tS" - Transparent Parameters Menu
The card is equipped with 24 transparent parameters also modifiable from Remote Con-
trol (Service Menu):
Remote
Card
Description of transparent parameters
Control
01
P01
Gas type selection
02
P02
Boiler type selection
03
P03
Absolute min. power
04
P04
Lighting power
05
P05
Not used
06
P06
Heating train
07
P07
Heating pump Post-Circulation
08
P08
Heating standby time
09
P09
Max. heating power
10
P10
Pump operation
11
P11
Pump deactivation temperature during Post-
Circulation
12
P12
Max heating temperature
13
P13
DHW pump Post-Circulation
14
P14
DHW standby time
A
B
15
P15
DHW max. power
16
P16
DHW user max. setpoint
17
P17
Hot water tank activation hysteresis tempera-
ture
18
P18
Hot water tank preparation delivery tempera-
ture
19
P19
Not used
20
P20
Not used
21
P21
Not used
22
P22
Legionella protection
23
P23
Not used
24
P24
Mains Voltage Frequency
Press the Heating buttons to scroll the list of parameters in increasing or decreasing or-
der. Press the DHW buttons to modify the value of a parameter: the change will be au-
tomatically saved.
The Max. Heating Power and Lighting Power parameters can be modified in Test Mode
(see relevant section).
Press the Reset button to return to the Service Menu. Press the Reset button for 10 sec-
onds to exit to the card Service Menu.
"In" -Information menu
The card can display the following information:
t01
Heating NTC sensor (°C)
t02
DHW NTC sensor (°C)
t03
Safety NTC sensor (°C)
t04
External NTC sensor (°C)
L05
Actual burner power (%)
P06
Actual system water pressure (bar/10)
F07
Actual ionisation current (uA)
Press the Heating buttons to scroll the list of information. In case of damaged sensor, the card
displays hyphens.
Default
Press the Reset button to return to the Service Menu. Press the Reset button for 10 seconds to
exit the Service Menu.
0=Copper
"Hi" - History menu
0°C
The card can store the last 10 faults: the History datum item H1: represents the most recent fault
that occurred; the History datum item H10: represents the least recent fault that occurred.
The codes of the faults saved are also displayed in the corresponding menu of the Opentherm re-
mote control.
Press the Heating buttons to scroll the list of faults. Press the DHW buttons to display the value.
Press the Reset button to return to the Service Menu. Press the Reset button for 10 seconds to
exit the Service Menu.
"rE" - History reset
Press the M button for 3 seconds to delete all the faults and times stored in the History Menu: the
card will automatically exit the Service Menu, in order to confirm the operation.
Press the Reset button to return to the Service Menu.
ALPA 31 BS 60
Range
Default
0=Natural gas
0=Natural gas
1=LPG
1=Heating only
2=Storage with
2=Storage with probe
probe
3=Storage with ther-
most.
0-100%
0%
0-60%
50%
Not modifiable
0
1-20°C/min
5°C/min
0-20 minutes
6 minutes
0-10 minutes
2 minutes
0-100%
100%
0=Post-Circulation
0=Post-Circulation
1=Continuous
0-100°C
20°C
31-85°C
85°C
0-255 seconds
30 seconds
0-255 seconds
120 seconds
0-100%
100%
55-65°C
65°C
0-20°C
2°C
70-85°C
80°C
Not modifiable
0
Not modifiable
4 bar/10
Not modifiable
8 bar/10
0-7
0
Not modifiable
0
0=50Hz
0=50Hz
1=60Hz
between 05 and 125 °C
between 05 and 125 °C
between 05 and 125 °C
between -30 and 70°C (Negative values flash)
00%=Min., 100%=Max.
00=Pressure switch open
14= Pressure switch closed
00=burner off