Default I/O Connections - ABB ACQ580 Serie Guía Rápida De Inicio

Ocultar thumbs Ver también para ACQ580 Serie:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 117
104

Default I/O connections

Default I/O connections of the Water default configuration are shown below.
R0-
R4
1...10 kohm
R5
R6-
max.
R9
500 ohm
EN
DE
ES
FR
IT
RU
SV
Total load capacity of the Auxiliary voltage output +24V (X2:10) is 6.0 W (250 mA / 24 V DC).
Wire sizes:
2
0.2...2.5 mm
(24...14 AWG): Terminals +24V, DGND, DCOM, B+, A-, DGND, Ext. 24V
2
0.14...1.5 mm
Tightening torques: 0.5...0.6 N·m (0.4 lbf·ft)
X1
Reference voltage and analog inputs and outputs
1
2
3
4
5
6
7
8
9
X2 & X3
Aux. voltage output and programmable digital inputs
10
11
12
13
14
15
16
17
18
X6, X7, X8 Relay outputs
19
20
21
22
23
24
25
26
27
X5
Embedded fieldbus
29
30
31
S4
S5
X4
Safe torque off
34
35
36
37
38
(26...16 AWG): Terminals DI, AI, AO, AGND, RO, STO
SCR
Signal cable shield (screen)
AI1
Output frequency/speed reference: 0...10 V
AGND
Analog input circuit common
+10V
Reference voltage 10 V DC
AI2
Actual feedback: 0...10 V
AGND
Analog input circuit common
AO1
Output frequency: 0...10 V
AO2
Output current: 0...20 mA
AGND
Analog output circuit common
+24V
Aux. voltage output +24 V DC, max. 250 mA
DGND
Aux. voltage output common
DCOM
Digital input common for all
DI1
Stop (0) / Start (1)
DI2
Not configured
DI3
Constant frequency/speed selection
DI4
Not configured
DI5
Not configured
DI6
Not configured
RO1C
Ready run
RO1A
250 V AC / 30 V DC
2 A
RO1B
RO2C
Running
250 V AC / 30 V DC
RO2A
2 A
RO2B
RO3C
Fault (-1)
250 V AC / 30 V DC
RO3A
2 A
RO3B
B+
Embedded fieldbus, EFB (EIA-485)
A-
DGND
TERM
Termination switch
BIAS
Bias resistors switch
OUT1
Safe torque off. Factory connection. Both circuits
OUT2
must be closed for the drive to start. See chapter
The Safe torque off function in ACQ580-01 (0.75
SGND
to 250 kW) hardware manual (3AXD50000035866
IN1
[English]).
IN2
Tabla de contenido
loading

Tabla de contenido