Mitsubishi Electric PAC-SF44SRA Libro De Instrucciones página 11

Ocultar thumbs Ver también para PAC-SF44SRA:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 104
(8) Local remote controller operation prohibit setting
[Collective Setting/Monitor Screen]
1. Operations with all local remote controllers controlled with this controller can be prohibited.
[Group Setting/Monitor Screen]
1. Operations with the local remote controller for the selected group can be prohibited.
When this controller's SW3-5 operation prohibit range setting changeover has been set
to "ON (including system controller)", operations of the other system controllers can be
prohibited.
Setting method: Set on the [Collective Setting/Monitor Screen] or [Group Setting/Monitor Screen].
1. When the PROHIBIT switch is pressed, [ PROHIBIT , ON/OFF, MODE, TEMP., FILTER ]
will appear. Items that have already been prohibited will turn ON, and the permitted items will
flicker. All items will flicker on the [Collective Setting/Monitor Screen].
If the group is controlling LOSSNAY, [MODE, TEMP. ] will not appear.
2. Set the items to be prohibited or permitted with local remote controller operations.
• To prohibit or permit ON/OFF operations
Press the ON/OFF switch. The ON/OFF display will change when pressed.
• To prohibit or permit operation mode changeover
Press the MODE switch. The "MODE" display will change when pressed.
• To prohibit or permit room temperature adjustment
Press the TEMP.
The "TEMP" display will change when pressed.
• To prohibit or permit filter resetting operations
Press the FILTER switch. The "FILTER" display will change when pressed.
[Changes in display of each item] Flicker (Not set) → ON (Prohibit) → OFF (Permit)
When each item's switch is pressed, the related display will change as shown above from the
current display state.
[Meaning of displays]
Display
ON/OFF Local remote controller ON/OFF operation prohibited
MODE
Local remote controller operation mode changeover prohibited
TEMP.
Local remote controller room temperature adjustment prohibited Local remote controller room temperature adjustment permitted
FILTER Local remote controller filter resetting prohibited
3. The prohibited or permitted item will be set when the PROHIBIT switch is pressed, and local
remote controller operation of the items that are ON will be prohibited. The operation will be
permitted if the item is OFF or flickering (not set).
(*1) On the [Collective Setting/Monitor Screen], if all four items are flickering in step 3 above (nothing is
being operated), it does not mean that all operations are permitted. Instead this means that the previous set-
tings will be applied.
1. This function can be set only when this controller's SW-4 operation prohibit setting
changeover is set to "ON (Permit)". Settings cannot be made when set to prohibited.
If the function is used when the setting is prohibited, [- CENTRALIZED -], PROHIBIT ,
ON/OFF, MODE, TEMP., FILTER] will flicker.
2. The operation mode changeover and room temperature adjustment operations can-
not be prohibited for LOSSNAY groups.
:
:
:
or
switch.
:
ON
OFF or flickering (*1)
Local remote controller ON/OFF operation permitted
Local remote controller operation mode changeover permitted
Local remote controller filter resetting permitted
11
Tabla de contenido

Solución de problemas

loading

Tabla de contenido