Additional Refrigerant Charge; Drainage Piping Work; Electrical Work; Wiring Transmission Cables - Mitsubishi Electric PUMY-P-YHM Serie Manual De Instalación

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 42
4. Installing the refrigerant piping

4.6. Additional refrigerant charge

Refrigerant of 3 kg equivalent to 50 m total extended piping length is already included
when the outdoor unit is shipped. Thus, if the total extended piping length is 50 m or
less, there is no need to charge with additional refrigerant.
Calculation of Additional Refrigerant Charge
• If the total extended piping length exceeds 50 m, calculate the required additional
refrigerant charge using the procedure shown below.
• If the calculated additional refrigerant charge is a negative amount, do not charge
with any refrigerant.
<Additional Charge>
Additional
Liquid pipe size
refrigerant charge
Total length of
ø9.52 × 0.06
=
(m) × 0.06 (kg/m)
(kg)

5. Drainage piping work

Outdoor unit drainage pipe connection
When drain piping is necessary, use the drain socket or the drain pan (option).
Drain socket
Drain pan

6. Electrical work

6.1. Caution
1 Follow ordinance of your governmental organization for technical standard re-
lated to electrical equipment, wiring regulations and guidance of each electric
power company.
2 Wiring for control (hereinafter referred to as transmission line) shall be (5 cm or
more) apart from power source wiring so that it is not influenced by electric noise
from power source wiring. (Do not insert transmission line and power source wire
in the same conduit.)
3 Be sure to provide designated grounding work to outdoor unit.
4 Give some allowance to wiring for electrical part box of indoor and outdoor units,
because the box is sometimes removed at the time of service work.
5 Never connect the main power source to terminal block of transmission line. If
connected, electrical parts will be burnt out.
6 Use 2-core shield cable for transmission line. If transmission lines of different
systems are wired with the same multiplecore cable, the resultant poor transmit-
ting and receiving will cause erroneous operations.
L1 L2 L3 N
M1
M2
S
M1
M2
S
A
TB3
TB7
B
Fig. 6-1

6.3. Wiring transmission cables

1 Types of control cables
1. Wiring transmission cables
• Types of transmission cables: Shielding wire CVVS or CPEVS
• Cable diameter: More than 1.25 mm
• Maximum wiring length: Within 200 m
2. M-NET Remote control cables
Kind of remote control cable
Shielding wire MVVS
0.5 to 1.25 mm
Cable diameter
When 10 m is exceeded, use cable with the
Remarks
same specifications as transmission line wiring
8
Liquid pipe size
Refrigerant
Total length of
amount for
ø6.35 × 0.024
outdoor unit
+
(m) × 0.024 (kg/m)
3.0 kg
P100-140
PAC-SG61DS-E
PAC-SG64DP-E
A : Power source
B : Transmission line
2
2
<Example>
Outdoor model : 125
Indoor 1 : 63
A : ø9.52
30 m
2 : 40
3 : 25
4 : 20
The total length of each liquid line is as follows
ø9.52 : A + a = 30 + 15 = 45 m
ø6.35 : b + c + d = 10 + 10 + 20 = 40 m
Therefore,
<Calculation example>
Additional
refrigerant charge = 45 × 0.06 + 40 × 0.024 – 3.0 = 0.7 kg (rounded up)
7 Only the transmission line specified should be connected to the terminal block for
outdoor unit transmission.
(Transmission line to be connected with indoor unit : Terminal block TB3 for trans-
mission line, Other : Terminal block TB7 for centralized control)
Erroneous connection does not allow the system to operate.
8 In case to connect with the upper class controller or to conduct group operation in
different refrigerant systems, the control line for transmission is required between
the outdoor units each other.
Connect this control line between the terminal blocks for centralized control. (2-
wire line with no polarity)
When conducting group operation in different refrigerant systems without con-
necting to the upper class controller, replace the insertion of the short circuit
connector from CN41 of one outdoor unit to CN40.
9 Group is set by operating the remote controller.
6.2. Control box and connecting position of wiring
(Fig. 6-1)
1. Connect the indoor unit transmission line to transmission terminal block (TB3), or
connect the wiring between outdoor units or the wiring with the centralized con-
trol system to the centralized control terminal block (TB7).
When using shielded wiring, connect shield ground of the indoor unit transmis-
sion line to the earth screw (
) and connect shield ground of the line between
outdoor units and the central control system transmission line to the shield (S)
terminal of the centralized control terminal block (TB7) shield (S) terminal. In
addition, in the case of outdoor units whose power supply connector CN41 has
been replaced by CN40, the shield terminal (S) of terminal block (TB7) of the
centralized control system should also be connected to the ground (
2. Conduit mounting plates (ø27) are being provided. Pass the power supply and
transmission wires through the appropriate knock-out holes, then remove the
knock-out piece from the bottom of the terminal box and connect the wires.
3. Fix power source wiring to terminal box by using buffer bushing for tensile force
(PG connection or the like).
3. MA Remote control cables
2-core cable (unshielded)
Kind of remote control cable
Cable diameter
0.3 to 1.25 mm
2 Wiring examples
• Controller name, symbol and allowable number of controllers.
Name
Symbol
Outdoor unit controller
OC
Indoor unit controller
IC
RC
Remote controller
(M-NET)
MA
a : ø9.52
15 m
At the conditions
b : ø6.35
10 m
below:
c : ø6.35
10 m
d : ø6.35
20 m
).
2
Allowable number of controllers
One to eight controllers for one OC
Maximum of 16 controllers for one
OC
Maximum of two per group
Tabla de contenido
loading

Tabla de contenido