hager SM103E Instrucciones De Uso página 17

Tabla de contenido
Installation - Installation - Installation - Installazione -
Installering - Instalación - Instalação
Option modules
The SM103E product can be fitted with option modules:
- Pulse outputs (ref: SM201)
2 pulse outputs connected to the metering of energy in kWh, kvarh and KVAh.
(User manual ref: 6S5073).
- Inputs/Outputs (ref: SM202)
2 outputs allocated for alarms, for voltage, current, power, power factor
and THD, or remote control. 2 inputs for the metering of pulses or
controlling position.
(User manual ref: 6S5074).
- Analogue outputs (ref: SM203)
2 analogue outputs 4/20 mA or 0/20 mA configurable for current, vol-
tage, power and power factor. 2 modules can be installed, a maximum
of 4 outputs.
(User manual ref: 6S5075).
- Storage capability (ref: SM204)
Storage capability for storing mean active and reactive power, minimum
and maximum instantaneous values, the last 10 alarms, troughs/overvol-
tages and power cuts according to EN50160.
(User manual ref: 6S5076).
- Temperature (ref: SM205)
PT100 Technology.
4 temperature indicators:
• 1 internal,
• 3 external (PT100 input).
(User manual ref: 6S5077).
17
- JBUS/MODBUS communication (ref: SM211)
RS485 JBUS/MODBUS serial port in RTU mode with a speed from
2400 to 38400 baud.
(User manual ref: 6S5079).
- Ethernet (ref: SM213)
100 base-T connection with RJ45 connector. Modbus protocol TCP , WEB
server for product configuration.
(User manual ref: 6S5080).
- Ethernet + RS485 (ref: SM214)
RS485 gateway function (RJ45/RS485 connector). JBUS/MODBUS/
3-pin to Ethernet. WEB server for product configuration.
(User manual ref: 6S5080).
Tabla de contenido
loading

Tabla de contenido