Town Gas G110 – Industrial gas. The setting of this function is used to ad
just the boiler in order to function with gases from the first family.
Town Gas G110 - Industrial gas (first family gas)
Off (Standard setting)
On
3.8
Automatic slow startup function with timed ramp delivery.
In the ignition phase the electronic control board carries out an increasing gas
delivery ramp (with pressure values that depend on the type of gas selected)
of preset duration. This avoids the need to carry out boiler ignition phase
calibration or preparation operation in any conditions of use.
3.9
"Chimney Sweep" Function.
When activated, this function forces the boiler at max. output for 15
minutes.
In this mode all the adjustments are cut out and only the temperature
safety thermostat and the limit thermostat remain active. To activate the
"Chimney-Sweep" function, press the Reset key for 8 to 15 seconds in
absence of domestic water and heating requests. Its activation is indicated
by the simultaneous flashing of LEDS (2) and (3). This function allows the
technician to check the combustion parameters. After the checks deactivate
the function, switching
the boiler off and then on again.
3.10 Pump anti-block function.
If the main selector is set on "domestic water" (
function that makes the pump start at least once every 24 hours for 2.5
minutes in order to reduce the risk of the pump blocking due to extended
inactivity.
If the main selector is set on "domestic water -heating"
(
) the boiler has a function that makes the pump start at least once
every 3 hours for 2.5 minutes.
3.11 Three-way anti-block system
Both in "domestic" and in "domestic-heating" phase the boiler is equipped
with a function that starts the three-way motorized group 24 hours after it
was last in operation, running it for a full cycle so as to reduce the risk of
the three-way group becoming blocked due to prolonged inactivity.
3.12 Radiator antifreeze function.
If the system return water is below 4°C, the boiler starts up until it reaches
42°C.
3.13 Electronic board periodical self-check.
During operation in heating mode or with boiler in standby, the function
activates every 18 hours after the last boiler check/feed. In case of operation
in domestic circuit mode the self-check starts within 10 minutes after the
end of the drawing in progress, for a length of approx. 10 seconds.
NB: During self-check, the boiler remains off, including signalling.
LED
flashing
(slow)
LED 1
LED 8
) the boiler has a
ES
PL
TR
RO
IE
83