DTS cooling unit assembly (side attachment)
1
Figure 8 - Switch cabinet exterior view
Holes for DTS cooling unit
Item
Designation
1
Holes
3
Cut-outs
Make cut-outs for the DTS cooling unit
Requirements
-
All general requirements have been fulfilled; see
-
The unit is de-energized.
Required tools and material
-
Saw
-
Use a switch cabinet cutter, if applicable
-
Protective covers
Procedure
Use a protective cover to protect the switch cabinet from chips.
Provide the switch cabinet with cut-outs (3) and holes (1). For the prescribed dimensions, refer to the figure
exterior view of the switch cabinet.
Deburr the cut edges.
Remove chips and assembly waste from the switch cabinet.
Cut-outs and holes have been made.