GB
3.4.1
General assembly requirements
The following general requirements must be followed for safe and reliable operation of the cooling units:
Select an assembly location for the switch cabinet which will guarantee adequate ventilation of the cooling unit.
A minimum clearance of 200 mm between units and the nearest wall must be observed.
Installed components in the switch cabinet must not impede air circulation.
Secure the switch cabinet against tipping.
Ensure that provided hinges can support the additional weight of the cooling unit.
The cooling unit can be assembled with and without an external unit cover.
Protect the installation location from heavy contamination with covers.
3.4.2
Mounting M8 jack rings
WARNING
Danger of accidents due to unapproved crane transport
Movement of switch cabinets with integrated cooling units can result in accidents.
Only lifting by M8 jack rings is permitted for the cooling unit.
Ensure that jack rings and unit threads are not damaged or deformed.
Only use jack rings with an adequate thread length and ensure that they are securely seated.
The cooling units have threads for M8 jack ring installation. M8 jack rings can be installed in cooling units for crane
transport.
Item
Designation
1
DTS cooling unit M8 jack rings
Requirements
-
The factory-provided packaging has been removed from the cooling units.
-
Observe the minimum screw depth of the M8 jack rings.
-
M8 jack rings and cooling unit threads must be free from damage (corrosion and deformation).
-
The unit cover screws (2) have been removed.
Procedure
Screw in the two M8 jack rings (1) completely with the appropriate thread depth.
Check to ensure the proper seating of the M8 jack rings in the cooling unit.
The M8 jack rings are screwed in the cooling unit and the unit can be moved.
Operating Manual DTS and DTI 6401 / 6501 Standard Controller (SC) 086100007 © Pfannenberg GmbH
1
Figure 7 - DTI/DTS cooling unit M8 jack rings
Item
1
2
Designation
2
Unit cover screws
Page 15 / 38