Settings on the " Heating engineer's" level
Press
and
simultaneously for 3 seconds, thus activating the "Heating engineer's" level
for setting the plant type and the plant-related variables.
Setting the plant type on operating line 51:
The required plant type must be set on operating line 51 using buttons
vates all functions required for the respective type of plant and shows the associated operating
lines.
Display example:
51
Plant type
Plant types
A6
Room unit
B1
Flow or boiler temperature sensor
B5
Room temperature sensor
B7
Return temperature sensor (primary circuit)
B71 Return temperature sensor (secondary circuit)
B9
Outside sensor
E1
Boiler or heat exchanger
E2
Load
LPB Data bus (Local Process Bus)
M1 Circulating pump or boiler pump
N1
Controller RVL480
Y1
Actuator for seat or slipper valve
Building Technologies
2 = Plant type 2
1
(1...6)
.........................
74 319 0617 0 a
100 = two clock time masters on
the data bus
120 = flow alarm
140 = wrong controller address
(LPB)