Riello RL 190/M Instrucciones De Instalación, Uso Y Mantenimiento página 11

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

D3760
(A)
a - d : red
b - c : white
(B)
Model
RL 190/M - 220 V
RL 190/M - 380 V
(C)
RL 190/M
208-230 V
F
A
T25
L
2
2,5
mm
D1910
Calibration of thermal cut-out
16 A
9.5 A
9
LAYOUT (A)
RL 190/M electrical connection three-phase
380/460 V power supply with neutral phase
wire
Fuses and cables section layout (A), see table.
Cable section not indicated: 1.5 mm
LAYOUT (B)
Power regulator RWF40 electrical connec-
tion (modulating operation)
Key to wiring layouts (A) - (B)
BT - Temperature probe
BP - Pressure probe
IN - Manual burner stop switch
MB - Terminal strip
S
- Remote lock-out signal
TL - Limit control device system: this shuts
down the burner when the boiler tempera-
ture or pressure exceeds the setpoint
value.
TR - Load control device system: controls mini-
mum and maximum power. The TR load
control is not required when the regulator
RWF40 is connected as its function is per-
formed by the regulator RWF40 itself.
TS - Safety control device system: this oper-
ates when TL is faulty.
380-460 V
N.B.
T25
The supply to the auxiliary circuits must be 230 V.
2,5
The RL 190/M burner has been type- approved
for intermittent operation. This means they
should compulsorily be stopped at least once
every 24 hours to enable the control box to per-
form checks of its own efficiency at start-up.
Burner halts are normally provided for automati-
cally by the boiler load control system.
If this is not the case, a time switch should be fit-
ted in series to IN to provide for burner shut-
down at least once every 24 hours.
These burners are also fitted for continuous
operation, if they are equipped with control box
LANDIS type LOK 16.250 A27 (interchangeable
with the burner control box LANDIS LAL 1.25).
WARNING: Do not invert the neutral with the
phase wire in the electricity supply line.
2