6 Commissioning
6.6.8 TCS-FP microcontroller PCB
1
2 3
4
E
F
A
B
C
Fig. 15
TCS-FP microcontroller PCB
If safety devices (e.g., emergency stop switch) are not used, a jumper between terminal clamps A and B as well as
between C and D must be integrated; or sliding switches E and F must be switched to the ON position.
If safety devices (e.g., emergency stop switch) are used, sliding switches E and F must be switched to the OFF position.
The safety device must connect clamps A and B (24-V operating voltage) and clamps C and D (GND) in operating mode.
LED Color
Status Description
1
Green
On
Off
2
Green
On
Off
3
Orange
On
Off
4
Green
On
Off
5
Green
On
Off
6
Green
On
Off
7
Green
On
Off
8
Orange
On
Off
Tab. 14
LED status module
EN - 22
5
6
7
8
9
D
"Start+" signal is active
"Start+" signal is not active
"Start+" signal is active
"Start+" signal is not active
"Ready" output is active
"Ready" output is not active
"S3 collet is closed" end switch was tripped
"S3 collet is closed" end switch was not tripped
"S4 stroke cylinder is up" end switch was tripped
"S4 stroke cylinder is up" end switch was not tripped
"S1 stroke cylinder is down" end switch was tripped
"S1 stroke cylinder is down" end switch was not tripped
"S2 collet is open" end switch was tripped
"S2 collet is open" end switch was not tripped
"Y2 close clamping cylinder and motor on" output is active
"Y2 close clamping cylinder and motor on" output is not active
10
11
12
13 14 15 16
BAL.0713.0 • 2019-02-11