9.5) MENU LINGUA (lingua)
Used to set the programmer's language on the display.
9.6) MENU AUTOSET (AUTOset) FIG.V
• Launch an autoset operation by going to the relevant menu.
• As soon as you press the OK button, the ".... .... .... " message is displayed and the control
unit commands the device to perform a full cycle (opening followed by closing), dur-
ing which the minimum torque value required to move the leaf is set automatically.
During this stage, it is important to avoid breaking the photocells' beams and not
to use the START and STOP commands or the display.
Once this operation is complete, the control unit will have automatically set the
optimum torque values. Check them and, where necessary, edit them as described
in the programming section.
WARNING!! Check that the force of impact measured at the points
provided for by standard EN 12445 is lower than the value laid down
by standard EN 12453.
Warning!! While the autoset function is running, the obstacle detection
function is not active. Consequently, the installer must monitor the
automated system's movements and keep people and property out of range
of the automated system.
9.7) MENU REGOLAZIONE FINECORSA FIG. U
The VENERE D control panel has an opening and closing limit switch adjustment
menu, which simplifies the installation procedure.
Proceed as follows:
• Launch a limit switch adjustment operation by going to the relevant menu
on the VENERE D panel (Fig.B).
• When the " CLOSE" message is displayed, move the door to the desired closed
position using the "UP" and "DOWN" buttons on the control unit, bearing in
mind that the "DOWN" button closes the door, while the "UP" button opens
the door. As soon as the door is in the desired closed position, press the "OK"
button to store the closed travel limit position.
• When the "OPEN" message is displayed, move the door to the desired open
position using the "UP" and "DOWN" buttons on the control unit, bearing in
mind that the "DOWN" button closes the door, while the "UP" button opens
the door.
As soon as the door is in the desired open position, press the "OK" button to
store the open travel limit position.
• Position the " runner stop" correctly up against the runner and secure in place
with the screws (fig.U rif.6 A-B).
NOTE: These operations must be performed in "deadman" mode at reduced
speed and without the safety devices operating.
TABLE "A" - PARAMETERS MENU - (PARA )
Parameter
min.
max.
Default
180
TCA
 1
99
Op. T orque
 1
99
Cls. T orque
000.1 006.0
part. o pen
0
127
zona
70
99
op speed
70
99
cl speed
7
100
dist. s loud
Editing one of the following parameters:
- Running speed during opening
- Running speed during closing
- Slow-down distance
results in the actuator performing a complete opening/closing cycle with the anti-crush feature switched off. The "SET" message flashes on the display to warn that
this cycle is in progress.
INSTALLATION MANUAL
Personal
Definition
Automatic
40
 
Closing Time [s]
Opening torque
50
 
[%]
Closing torque
50
 
[%]
Partial opening
001.0
[m]
0
Zona
Running speed
99
during opening
[%]
Running speed
99
during closing
[%]
Slow-down
7
distance [cm]
9.8) STATISTICS
Connect the UNIVERSAL HANDHELD programmer to the control unit, enter the
CONTROL UNIT/STATISTICS menu and run through the statistics parameters screen:
-
Software version of card microprocessor.
-
Number of cycles performed. If the motors are replaced, write down the
number of operations performed so far.
-
Number of cycles performed since last service. Automatically reset every time
self-diagnosis is run or parameters are written.
-
Date of last service. Must be updated manually via the relevant "Update service
date" menu
-
System description. Allows for 16 characters to be entered to identify the
system.
10) REMOTE TRANSMITTER PROGRAMMING FIG. X
This mode does not require access to the control panel.

11) SERIAL CONNECTION VIA SCS1 CARD (Fig.Y)

The VENERE D control panel's special serial inputs and outputs (SCS1) make the
centralized connection of a number of automated devices possible. That way, all the
automated devices connected can be opened or closed with a single command.
Connect all VENERE D control panels using twisted pair cabling only, proceeding
as shown in the diagram in Fig. Y.
When using a telephone cable with more than one pair, it is essential to use wires
from the same pair.
The length of the telephone cable between one unit and the next must not
be greater than 250 m.
At this point, each VENERE D control panel needs to be configured appropriately,
starting by entering a MASTER control panel that will have control over all the
others, which therefore have to be set as SLAVE units (see logic menu).
Also set the Zone number (see parameters menu) in the range 0 to 127.
The zone number allows you to create groups of automated devices, each of
which answers to the Zone Master. Each zone can have only one Master: the
Master of zone 0 also controls the Slaves of the other zones.
12) FUSE REPLACEMENT FIG. Z
13) ACCESSORIES FIG. Z1
SM1
External release device to be applied to the cremone bolt already fitted
to the overhead door (1).
SET/S External release device with retracting handle for sectional doors mea-
suring max 50mm (2).
ST
Automatic bolt release device for spring-operated overhead doors. Fitted
to the control arm, it automatically releases the side door bolts (3).
Set the numerical value of the automatic opening time in the range 1 to 180 seconds.
Set the numerical value of the motor's opening torque in the range 1% to 99%.
WARNING: Check that the force of impact measured at the points provided for
by standard EN 12445 is lower than the value laid down by standard EN 12453.
Setting sensitivity incorrectly can result in damage to property and injury to
people and animals.
Set the numerical value of the motor's closing torque in the range 1% to 99%.
WARNING: Check that the force of impact measured at the points provided for
by standard EN 12445 is lower than the value laid down by standard EN 12453.
Setting sensitivity incorrectly can result in damage to property and injury to
people and animals.
Set the numerical value of partial opening in the range 10 cm (0.001) to 6 m (006.0)
Set the zone number between a minimum value of 0 and a maximum value of 127.
See section 11 entitled "Serial connection".
Sets the maximum opening speed reached by the actuator at running speed.
The value is given as a percentage of the maximum speed the actuator can reach.
Sets the maximum closing speed reached by the actuator at running speed.
The value is given as a percentage of the maximum speed the actuator can reach.
Sets the slow-down distance travelled by the actuator during opening and clos-
ing.
Description